beautypg.com

English battery system, Surge protection and filtering, Environmental – Minuteman UPS Enterprise Plus Series User Manual

Page 25: Physical, Regulatory compliance

background image

24

English

BATTERY SYSTEM

Typical Recharge Time

Typical Battery Life

Battery: Quantity/Rating

3-5 years, depending on discharge cycles and ambient temp

3-12V7.2Ah

3-12V8.5Ah

8-hours from total discharge

6-12V7.2Ah

Battery Type

Sealed, Non-Spillable, Maintenance Free, Value Regulated Lead Acid

System Voltage

36VDC

36VDC

72VDC

Runtime: Full Load (minutes)

Runtime: Half Load (minutes)

13

11

17

5

4

8

SURGE PROTECTION AND FILTERING

Audible Noise at 1 m (3 ft.)

10/100 Base-T surge protec-

tion let-through (as a percent-

age of an applied +/-6 kV 1.2/

50 us, 500 a 8/20 uS test)

Telephone line surge protec-

tion let-through (as a percent-

age of an applied +/-6 kV 1.2/

50 us, 500a 8/20 uS test)

Noise Filter

Surge voltage let-through (as

a percentage of an applied

ANSI C62.41 Cat. A +/-6 kV)

Surge Response Time

Surge Current Capability

Surge Energy Rating

800 J (600 J)

0 ns (instantaneous) normal mode; <5 ns common mode

<5%

normal and common mode EMI/RFI suppression

<45 dBA

<1%

<5%

6500 Amps total

ENVIRONMENTAL

Operating Temperature (max)

Operating/Storage Humidity

Operating Elevation

0 to 40

°

C (+32 to +104

°

F)

95% Non-Condensing

0 to 3,000m (0 to +10,000 ft)

PHYSICAL

Weight - Net

Size - Net
D X W X H

Size - Shipping
D X W X H

Weight - Shipping

46.2 lbs
21.0 Kgs

17.0 x 17.3 x 3.5"
432 x 440 x 89 mm

23.6 x 20.0 x 9.0"
600 x 508 x 230 mm

55.0 lbs
25.0 Kgs

REGULATORY COMPLIANCE

Safety and Approvals

EMC Verification

UL1778, cUL (CSA 22.2 no. 107.1)

FCC Class B, CE certified

Storage Elevation

0 to 15,000m (0 to +50,000 ft)

Storage Temperature

-15 to +45

°

C (+5 to +113

°

F)

36VDC

72VDC

3-12V7.2Ah

6-12V8.5Ah

8

3

15

5

<60 dBA

24.0 x 17.3 x 3.5"
610 x 440 x 89 mm

39.4 x 23.6 x 9.0"
1000 x 600 x 230 mm

110.9 lbs
50.4 Kgs

127.0 lbs
57.3 Kgs