beautypg.com

Miller Electric A.B.B. Robot Interface Gas Control Hub And Spindle User Manual

Page 30

background image

OM-884 Page 26

5-6.

Use Of Indicator Lights For Troubleshooting

Gas Indicator Light

On

Off

Gas flows:

Gas does not flow:

Gas flows:

Gas does not flow:

System normal (on.)

Check gas valve operation.

Check gas valve operation
and gas line for leaks.

System normal (off).

Check interface board PC3.

Contactor Indicator Light

On

Off

Contactor closed:

Contactor open:

Contactor open:

System normal (on).

Check interconnecting cords.

System normal (off).

Check interface board PC3.

Wire Feed Indicator Light

On

Off

Wire feeds:

Wire does not feed:

Wire feeds:

Wire does not feed:

System normal (on).

Check circuit breaker CB1.

System normal (off).

Check relay CR1.

Check interface board PC3.

Current Indicator Light

On

Off

Arc started:

No arc:

Arc started:

No arc:

System normal (on).

Replace reed relay.

Replace reed relay.

System normal (off).

Arc Failure Indicator Light

On

Off

No arc:

Arc started:

Normal during idling.

No arc:

Check weld

Check input signal from

Normal while welding.

Contactor closed:

Check display board PC4.

robot to motor board PC2.
Signal should be 0-10 vdc
between pins K and B
(common) at RC5.

Check motor board PC2.

Arc started:

Check signal from robot.

parameters.

Signal should be 24 vdc
between terminals 1 TL
and 1 TM.

Check display board PC4.