ADJUSTABLE FEATURES

SX TRANSISTOR CONTROLS

Page

61

January 2000

The ratio value (VAL) is the set value divided by 10 and

rounded to the whole number.

Example: Setting of 45 = 45/10 = 4.5 = 4 VAL

I

FIELD

= VAL ( I

MOTOR

x 0.029 )

FUNCTION 28

STORED STATUS CODE COUNT POINTER

( Push CONT 13)


This register contains the location of the last stored status
code recorded of the 16 stored status codes. These stored
status codes have caused a PMT controller shutdown
and/or disruption of normal vehicle operation.

To determine which stored status code was the last one

recorded, read the number stored in Function 28. Using the
Memory Map for your logic card, match the "stored status
code pointer number"
[the number shown in (bold italics)

in the HS (Handset) number column] on the memory map,

with the number obtained from Function 28. This will be the

last stored status code recorded.


Note: When scrolling through the stored status code
register, the register always starts at status code 1 and
scrolls to status code 16. Instructions for scrolling the
register are in section 6.3.2 of this instruction booklet.



FUNCTION 48

MODE 1 (TURTLE) - ARMATURE

CONTROLLED

ACCELERATION

( Push CONT 1)

This function allows for the adjustment of the rate of time it

takes for the control to accelerate to 100% applied battery

voltage to the motor on hard acceleration.

Range

0.025 to 6.3 seconds

Set

0 to 255

Resolution

0.025 seconds per set unit

Example:

Setting of 20 = 0.5 seconds

This C/A takes effect when the Mode 1 settings are called

for by the interactive Dash Display.



FUNCTION 49

MODE 1 FIELD WEAKENING START

( Push CONT 2)

This function allows for setting the armature current at

which minimum field current will achieved .

Range

0 to 414 Amps

Setting

0 to 255

Resolution

1.625 per set unit

Example: Setting of 20 = 32.5 amps

I

M

FWS = VAL x 1.625

This FIELD WEAKENING START takes effect when the

Mode 1 settings are called for by the interactive Dash

Display.


FUNCTION 50

MODE 1 FW RATIO

( Push CONT 3 )

This function sets the ratio between armature and field

current when transitioning from minimum field to maximum

field current. The setting represents the quantity of field

current changed for each 1 amp of armature current

changed.


Max Fld Ref

Set

Resolution Per Unit Value

40

0 to 10

0.029 amps


The ratio value (VAL) is the set value divided by 10 and

rounded to the lowest whole number.

Example : Setting of 45 = 45/10 = 4.5 = 4 VAL.

I

FIELD

= VAL ( I

MOTOR

X .029 )


This FW RATIO takes effect when the Mode 1 settings are

called for by the interactive Dash Display.


FUNCTION 51

MODE 1 MAX ARMATURE % ON

( Push CONT 4)

This function allows for the adjustment of the speed limit

(maximum battery volts to the motor) when the SL1 limit

switch input signal is received by the control card. The SL1

limit switch is a normally closed switch connected to

battery negative; the switch opening enables speed limit.

Range

100% to 0% battery volts

Set

51 to 180

Resolution

0.78 % per set unit

Example

Setting of 71 = 84.4 % battery

volts

This MAX ARMATURE % ON takes effect when the Mode 1

settings are called for by the interactive Dash Display.

The following functions have function numbers larger

than the numbers on the Handset keyboard. To access

these functions. Push the CONT key and the number

shown in the following instructions at the same time.

THE SEAT SWITCH MUST BE CLOSED.