DIAGNOSTIC STATUS CODES

TRANSISTOR PUMP CONTROL

Page 49

January 2000

PUMP

STATUS CODE

DESCRIPTION OF

STATUS

CAUSE OF STATUS INDICATION

-144

Power Transistor (Q1) did not
turn off properly.

This status code is displayed when, during pump control
operation, the transistor fails to turn off. This will result in a
PMT condition.

MEMORY RECALL

YES

CORRECTIVE ACTIONS

TROUBLE-SHOOTING DIAGRAM

Circuits valid

for

Pump

Controller


SYMPTOM
With no pump contactor, control
may run continuously.

POSSIBLE CAUSE
Control is defective.

=Replace controller unit.



POWER

CONNECTIONS

POS

A1

NEG

A2

FI

EL

D

ARMATURE

+

-

FU1

FU3

KEY SWITCH

P1

P2

P3

P12

LINE

FU6

P19

P21

TO

TRACTION

CARD

SPEED L

IMI

T 1

SPEED L

IMI

T 2

SPEED L

IMI

T 3

TO TRACTION

P10 - BDI

PY7

PY12
PY10
PY11

PUMP

STATUS CODE

DESCRIPTION OF STATUS

CAUSE OF STATUS INDICATION

-145

Power Transistor (Q1) did not turn on
properly.

This status code is displayed when during pump
control operation, the transistor fails to turn on.

MEMORY RECALL

YES

CORRECTIVE ACTIONS

TROUBLE-SHOOTING DIAGRAM

Circuits valid

for

Pump

Controller


SYMPTOM

With no pump contactor, the control
may run continuously.

POSSIBLE CAUSE
Control is defective.

=Replace controller unit.

POWER

CONNECTIONS

POS

A1

NEG

A2

FI

EL

D

ARMATURE

+

-

FU1

FU3

KEY SWITCH

P1

P2

P3

P12

LINE

FU6

P19

P21

TO

TRACTION

CARD

SPEED L

IMI

T 1

SPEED L

IMI

T 2

SPEED L

IMI

T 3

TO TRACTION

P10 - BDI

PY7

PY12
PY10
PY11