GE E4H-CE User Manual
Page 11
7
Table 2.1
Alarm Messages
*
Set at factory.
ALARM
DISPLAYED
LOW INLET
PRESSURE
HI PERMEATE
PRESSURE
HI TEMP
HIGH
pH
HIGH
CONDUCTIVI-
TY
MOTOR 1
START
FAILURE
E-STOPPED
PRESSED
ACTION
Shuts down RO
machine
Shuts down RO
machine
Shuts down RO
machine
Alarm light dis-
played on pH
meter
Shuts down RO
machine
Shuts down RO
machine
Shuts down RO
machine
NOTES
Press ALARM
RESET on OIT
Press ALARM
RESET on OIT
Press ALARM
RESET on OIT
RO machine will
operate in alarm
condition
RO machine will
operate in alarm
condition
Press ALARM
RESET on OIT
and on Control
enclosure
Press ALARM
RESET on OIT on
OIT and on Control
enclosure
DISPLAY
(seconds)
12
0
0
None
None
0
None
FACTORY SET
POINTS*
Adjustable switch
[set at 0.8 bar
(12 psi)]
Adjustable switch
[set at 5.5 bar
(80 psi)]
Non-adjustable
switch [set at 38°C
(100°F)]
Adjustable switch
(set at 8.5)
Adjustable
(set at 50)
Adjustable
N/A