Network Parameter Errors
The following errors codes may be returned in bits 0—6 in the Get Slave Status reply.
Note: The error code is the numerical value of the bits.
Error
Code
Meaning
0 No
error
1
ID from master does not match Slave ID
2
Ready Time from Master does not match Slave Ready time
3
Master is requesting Freeze or Sync, which is not supported
by the slave
4
Length of data from master to slave is incorrect
5
Length of data from slave to master is incorrect
6
One of the watchdog factors (SlvWdFact1 or SlvWdFact2)
from the master was 0.
7
Slave watchdog time out (check response timeout)
8
Slave timeout watchdog disabled from master