beautypg.com

Troubleshooting, Heater does not operate (direct spark) – Greenheck Fan VSU Make-Up Air Unit with Direct-Fired Gas Heater 470654 User Manual

Page 29

background image

29

Model VSU Make-Up Air

®

Heater Does Not Operate (Direct Spark)

Does not attempt to light (No visible spark)

Troubleshooting

24 VAC between

terminals W1 and X?

Heat switch (S4) off.

Turn heat switch (S4) on.

Heat switch not wired.

Wire heat switch (S4).

24 VAC between

terminals 22 and 21?

Main transformer (TR2) defective.

Replace transformer.

24 VAC between

terminals 26 and 21?

(Optional) high/low gas pressure switch(es)

(PS3 and PS4) tripped.

Correct gas pressure and reset.

Reference: Start-Up - Direct Gas, Check the Pilot Gas Pressure, pg. 15

24 VAC between

terminals 24 and 21?

High limit (HLC1) tripped.

Reset, replace high limit (HLC1).

Check on cause of control loss.

Continuity between

terminals 26 and 27?

24 VAC between

terminals 23 and 21?

(Optional) inlet air sensor (TS4) holding.

Adjust TS4 setting.

Reference: Start-Up - Blower, Set-Up Optional Components, pg. 15

Heat relay (RH) defective.

Replace heat relay (RH).

No

No

No

No

No

No

Yes

Yes

Yes

Yes

Yes

Airflow switch (PS2) holding for proper airflow.

Correct airflow across burner.

Reference: Start-Up - Direct Gas,

Check the Optional High and Low Gas Pressure Switches, pg. 15

Yes

At this time the heater should attempt to light.