Model VSU Make-Up Air

®

Direct Gas Burner Sequence - Pilot Ignition

1. Supply Fan Contact Closed

• Power passes to the supply fan and heat switch

2. Heat Contact Closed

• Power passes to the heat relay then to the Flame

Safeguard

3. Flame Safeguard (FSG) Sequence

• Checks for proper airflow

• Verifies no flame present at burner

• Initiates 10 second prepurge

• Sends power to open pilot gas valve (V1) and

energizes the spark generator (SG) (clicking of the
spark generator may be heard)

• Tries for up to 10 seconds to light pilot and

confirm flame

• Powers the main gas valves open

• Shuts down spark generator

• Continuously monitors the flame and airflow

• Performs self-diagnostic check every five

seconds.

Direct Gas Burner Sequence - Direct Spark

1. Supply Fan Contact Closed

• Power passes to the supply fan and heat switch

2. Heat Contact Closed

• Power passes to the heat relay then to the Flame

Safeguard

3. Flame Safeguard (FSG) Sequence

• Checks for proper airflow

• Verifies no flame present at burner

• Initiates 15 second prepurge

• Sends power to open gas valve (V2) and

energizes the spark generator (clicking of the
spark generator may be heard)

• Tries for up to 10 seconds to light and confirm

flame

• Shuts down spark generator

• Continuously monitors the flame and airflow

• Power passes to N.C. supply overload contact

(ST1 OL)

• Power passes through N.C. contact on optional

freeze protection timer (RT4) which remains
closed if the temperature has remained above the
set point

• Power passes to optional inlet damper which

opens

• When damper is fully opened, damper relay

(D1) is energized and optional N.O. damper limit
switch (DL1) closes

• Power passes to and energizes supply starter

relay (RF)

• Power passes to N.O. fan contact (RF), which is

energized and closed

• Supply starter (ST1) is energized

• Supply starter contact (ST1) closes and power

reaches and energizes supply fan

• Supply fan (M1) starts

3a. Heat Contact (S4) Closed - Pilot Ignition

• Power passes to N.O. fan relay (RF) which is

energized and closed

• Power passes to optional inlet air sensor contact

(TS4) which is energized and closed if the inlet air
temperature is below the set point

• Power passes to and energizes the heat relay

(RH)

• N.O. heat relay contact (RH) closes

• Power passes to and energizes terminal 5 of the

Flame Safeguard (FSG). Power light on FSG is on.

• Power passes to N.C. high limit control contact

(HLC1) which is closed if temperature has
remained below set point

• Power passes to optional N.O. and N.C. high and

low gas pressure contacts (PS4 and PS3), which
are both closed if gas pressure is within the set
range

• Power passes to terminal 6 of the Flame

Safeguard (FSG)

• Power begins direct gas burner sequence

(see Direct Gas Burner Sequence)

3b. Heat Contact (S4) Closed - Direct Spark

• Power passes to N.O. fan relay (RF) which is

energized and closed

• Power passes to optional inlet air sensor contact

(TS4) which is energized and closed if the inlet air
temperature is below the set point

• Power passes to and energizes the heat relay

(RH)

• N.O. heat relay contact (RH) closes

• Power passes to N.C. high limit control contact

(HLC1) which is closed if temperature has
remained below set point

• Power passes to optional N.O. and N.C. high and

low gas pressure contacts (PS4 and PS3), which
are both closed if gas pressure is within the set
range

• Power passes to N.O. and N.C. airflow switches

(PS2) which are closed if there is proper airflow
across the burner

• Power passes to terminal TH on the Flame

Safeguard (FSG) which begins it’s sequence
(see Direct Gas Burner Sequence)