Start-up - checklist – Greenheck Fan VSU Make-Up Air Unit with Direct-Fired Gas Heater 470654 User Manual
Page 13

13
Model VSU Make-Up Air
®
Unit Model Number _______________________________
(e.g. VSU-H20)
Unit Serial Number _______________________________
(e.g. 10111000)
Start-Up Date
_______________________________
Start-Up Personnel Name __________________________
Start-Up Company _______________________________
Phone Number
_______________________________
Pre Start-Up Checklist –
check boxes as items
are completed.
Check tightness of all factory wiring connections
Verify control wiring wire gauge
Hand-rotate blower to verify free rotation
Verify supply voltage to the main disconnect
Verify the supply gas pressure
Verify remote controls wiring
Check V-belt drive for proper alignment and
tension
Start-Up Blower Checklist –
refer to Start-Up -
Blower section for further detail.
Check line voltage
L1-L2 __________
L2-L3
__________
L1-L3
__________
Check blower rotation
Check for vibration
Supply fan RPM
_________ RPM
Motor nameplate amps
_________ Amps
Actual motor amps
_________ Amps
Actual CFM delivered
_________ CFM
Optional Accessories –
refer to Start-Up - Blower,
Set-Up Optional Components, pg. 15 for further detail.
Heating Inlet Air Sensor
________
Actual
Setting
Typical setting 60º-70ºF
Cooling Inlet Air Sensor
________
Actual
Setting
Typical setting 75ºF
Building Freeze Protection
________
Actual
Setting
Typical setting 5 minutes; 45ºF
Dirty Filter Gauge
________
Actual
Setting
Typical setting varies
Start-Up Direct Gas (Pilot Ignition) –
refer to
Start-Up - Direct Gas section for further detail.
Check supply gas pressure
________
Maximum
________
Minimum
________
Actual
Check Pilot Gas Pressure
________
Actual
Setting
Typical 3.0 in. wg
Set optional High Gas Pressure Switch
________
Actual
Setting
Typical 8.0 in. wg
Set optional Low Gas Pressure Switch
________
Actual
Setting
Typical 3.0 in. wg
Set Burner Pressure Differential
________
Actual
Setting
Typical 0.65 in. wg
Set the maximum firing rate
________
temp
rise
Set the minimum firing rate
________
check
Set the unit’s operating temperature
________
ºF
Start-Up Direct Gas (Direct Spark) –
refer to
Start-Up - Direct Gas section for further detail.
Check supply gas pressure
________
Maximum
________
Minimum
________
Actual
Set optional High Gas Pressure Switch
________
Actual
Setting
Typical 8.0 in. wg.
Set optional Low Gas Pressure Switch
________
Actual
Setting
Typical 3.0 in. wg.
Set Burner Pressure Differential
________
Actual
Setting
Typical 0.65 in. wg
Set the maximum firing rate
________
temp
rise
Set the minimum firing rate
________
check
Set the unit’s operating temperature
________
ºF
Start-Up - Checklist