APPENDIX A BLOWER PERFORMANCE TABLES
BELT DRIVE
STANDARD HORIZONTAL
CPG036 STANDARD BELT DRIVE HORIZONTAL
CFM
BHP
CFM
BHP
CFM
BHP
CFM
BHP
CFM
BHP
CFM
BHP
0.2
1524
0.32
1340
0.25
0.4
1628
0.41
1396
0.32
1171
0.24
900
0.16
0.6
1541
0.43
1284
0.32
1024
0.23
714
0.14
0.8
1444
0.45
1193
0.33
936
0.24
1.0
1111
0.34
806
0.23
1.2
744
0.22
CPG048 STANDARD BELT DRIVE HORIZONTAL
CFM
BHP
CFM
BHP
CFM
BHP
CFM
BHP
CFM
BHP
CFM
BHP
0.2
1800
0.47
1556
0.35
0.4
2002
0.65
1708
0.49
1438
0.36
1167
0.22
0.6
1910
0.67
1612
0.50
1330
0.37
1030
0.23
0.8
1813
0.69
1571
0.54
1222
0.36
989
0.25
1.0
1478
0.56
1142
0.32
1.2
1107
0.41
CPG060 STANDARD BELT DRIVE HORIZONTAL
CFM
BHP
CFM
BHP
CFM
BHP
CFM
BHP
CFM
BHP
CFM
BHP
0.2
2460
0.96
2251
0.80
2073
0.65
1862
0.51
0.4
2408
1.00
2206
0.84
1982
0.68
1808
0.55
1572
0.41
0.6
2402
1.08
2173
0.89
1943
0.72
1701
0.55
1511
0.43
0.8
2153
0.95
1917
0.77
1667
0.59
1.0
1888
0.82
1634
0.63
1.2
1601
0.67
CPG072 STANDARD BELT DRIVE HORIZONTAL
CFM
BHP
CFM
BHP
CFM
BHP
CFM
BHP
CFM
BHP
CFM
BHP
0.2
2749
1.18
2573
0.96
2402
0.79
0.4
2680
1.22
2544
1.06
2346
0.84
2164
0.68
0.6
2655
1.31
2498
1.10
2306
0.92
2094
0.72
1890
0.57
0.8
2703
1.47
2486
1.20
2263
0.97
2076
0.81
1.0
2515
1.34
2272
1.07
2002
0.83
1.2
2253
1.16
2028
0.93
NOTE
ESP, In
H
2
O
TURNS OPEN
0
1
2
3
4
5
Tables represent dry coil without filter, to compensate for filter add 0.08" to measured E.S.P.
SCFM correction for wet coil = 4 %.
ESP, In
H
2
O
TURNS OPEN
0
1
2
3
4
5
ESP, In
H
2
O
TURNS OPEN
0
1
2
3
4
5
ESP, In
H
2
O
TURNS OPEN
0
1
2
3
4
5