beautypg.com

Circulating air and filters d, Venting, Condensate drain connection c – Goodmans COMMERCIAL HEATING & COOLING 3 TON - 6 TON PACKAGE GAS UNIT CPG SERIES User Manual

Page 13: Warning, Caution

background image

13

NOTE: The gas connection size at the unit does NOT
establish the size of the supply line.

3. These units are designed for either natural or propane

(LP) gas and are specifically constructed at the factory
for only one of these fuels. The fuels are NOT
interchangeable. However, the furnace can be
converted in the field from natural gas to LP gas with
the appropriate factory kit (see unit Technical Manual
for the appropriate kit). Only a qualified contractor,
experienced with natural and propane gas systems,
should attempt conversion. Kit instructions must be
followed closely to assure safe and reliable unit
operation.

4. With all units on a common line operating under full

fire, natural gas main supply pressure should be
adjusted to approximately 7.0" w.c., measured at the
unit gas valve. If the gas pressure at the unit is greater
than 10.5" w.c., the contractor must furnish and install
an external type positive shutoff service pressure
regulator. The unit will not function satisfactorily if
supply gas pressure is less than 5.5" w.c. or greater
than 10.5" w.c..
NOTE: A minimum horizontal distance of 48"
between the regulator and the furnace flue discharge
is required.

5. With all units on a common line operating under full

LP gas main supply pressure should be at least 11.0"
w.c. and must be no greater than 13.0" w.c., measured
at the unit gas valve. Unit will not function satisfactorily
if supply gas pressure is less than 11.0" w.c. or greater
than 13.0" w.c..

6. All pipe connections should be sealed with a pipe

thread compound, which is resistant to the fuel used
with the furnace. A soapy water solution should be
used to check all joints for leaks. A tap is located on
the entering side of the gas valve for test gauge
connection to measure supply (main) gas pressure.
Another tap is provided on the manifold side of the
gas valve for checking manifold pressure.

T

HIS

UNIT

AND

ITS

INDIVIDUAL

SHUTOFF

VALVE

MUST

BE

DISCONNECTED

FROM

THE

GAS

SUPPLY

SYSTEM

DURING

ANY

PRESSURE

TESTING

OF

THAT

SYSTEM

AT

TEST

PRESSURES

IN

EXCESS

OF

1/2 PSIG (13.8”

W

.

C

.).

WARNING

T

HIS

UNIT

MUST

BE

ISOLATED

FROM

THE

GAS

SUPPLY

PIPING

SYSTEM

BY

CLOSING

ITS

INDIVIDUAL

MANUAL

SHUTOFF

VALVE

DURING

ANY

PRESSURE

TESTING

EQUAL

TO

OR

LESS

THAN

1/2

PSIG.

CAUTION

7. There must be no obstruction to prevent the flow of

combustion and ventilating air. A vent stack is not
required and must never be used. The power venter
will supply an adequate amount of combustion air as
long as the air passageways are kept free of any
obstructions and the recommended external unit
clearances are maintained.

CIRCULATING AIR AND FILTERS

D

UCTWORK

The supply duct should be provided with an access panel
large enough to inspect the air chamber downstream of the
heat exchanger. A cover should be tightly attached to pre-
vent air leaks.

Ductwork dimensions are shown in the roof curb installation
manual.

If desired, supply and return duct connections to the unit may
be made with flexible connections to reduce possible unit
operating sound transmission.

VENTING

NOTE: Venting is self-contained.

CONDENSATE DRAIN CONNECTION

C

ONDENSATE

D

RAIN

C

ONNECTION

A 3/4” NPT drain connection is supplied for condensate pip-
ing. An external trap must be installed for proper condensate
drainage.

DRAIN
CONNECTION

UNIT

2" MINIMUM

FLEXIBLE
TUBING-HOSE
OR PIPE

3" MINIMUM

A POSITIVE LIQUID
SEAL IS REQUIRED

Drain Connection

Install condensate drain trap as shown. Use 3/4" drain line
and fittings or larger. Do not operate without trap.

H

ORIZONTAL

D

RAIN

Drainage of condensate directly onto the roof may be ac-
ceptable; refer to local code. It is recommended that a small
drip pad of either stone, mortar, wood or metal be provided to
prevent any possible damage to the roof.

C

LEANING

Due to the fact that drain pans in any air conditioning unit
will have some moisture in them, algae and fungus will
grow due to airborne bacteria and spores. Periodic clean-
ing is necessary to prevent this build-up from plugging the
drain.