Goodmans COMMERCIAL HEATING & COOLING 3 TON - 6 TON PACKAGE GAS UNIT CPG SERIES User Manual
Page 28

28
APPENDIX A BLOWER PERFORMANCE TABLES
DIRECT DRIVE
CPG060 HORIZONTAL
SPEED
TAP
EXTERNAL STATIC
PRESSURE (ESP)
in w.c.
STANDAR D
CFM
AMPS
WATTS
RPM
0. 10
1416
1.63
176
588
0. 20
1295
1.61
174
621
0. 30
1200
1.68
186
660
0. 40
1133
1.79
196
704
0. 50
1045
1.90
208
753
0. 10
1543
2.00
220
627
0. 20
1485
2.12
236
671
0. 30
1425
2.20
250
698
0. 40
1352
2.26
258
748
0. 50
1304
2.39
274
786
0. 10
2107
4.02
502
797
0. 20
2031
4.13
518
819
0. 30
1980
4.27
536
858
0. 40
1954
4.37
554
880
0. 50
1887
4.48
572
913
0. 60
1839
4.58
582
940
0. 70
1782
4.72
602
968
0. 10
2224
4.73
592
832
0. 20
2165
4.79
612
860
0. 30
2123
4.91
630
891
0. 40
2079
5.01
642
913
0. 50
2029
5.14
666
946
0. 60
1978
5.26
676
969
0. 70
1926
5.38
698
1001
0. 80
1872
5.48
712
1028
0. 90
1817
5.58
722
1056
0. 10
2318
5.42
700
874
0. 20
2296
5.55
720
903
0. 30
2228
5.66
734
929
0. 40
2193
5.76
748
950
0. 50
2145
5.90
766
979
0. 60
2097
5.99
784
1012
0. 70
2054
6.10
798
1034
0. 80
1991
6.15
810
1050
0. 90
1952
6.26
826
1079
NOTES:
T5
CPG060 DIRECT DRIVE HORIZONTAL
Tables represent dry coil without filter, to compensate for filter add 0.08" to measured E.S.P. SCFM
correction for wet coil = 4 %. 5 Ton models are shipped from the factory with speed tap set on T4.
T1
T2
T3
T4