Ventilated Space Air Requirements for

U.S. Installations

Refer to Figure 5 (a), (b), (c) or (d) for proper sizing and
location of combustion air ducts and openings. CHECK
LOCAL CODES
.

a) Equipment located in ventilated spaces; all air from

inside the building.
Two permanent openings shall be provided connecting
to ventilated space (e.g. closet, small room) with the
unconfined space. Each opening shall be equal or
greater than 645cm

2

(100 in

2

.) with a width to height

ratio of 2:1. The top opening shall be located close to
the ceiling.

Note: The opening shall not be lower than the top of the
heater. The location of the bottom opening shall be 150-
450mm (6-18 in.) above floor level.

b) Basement installation, equipment located in ventilated

spaces; all air from outdoors.
Refer to the latest edition of the "National Fuel Gas
Code" ANSI Z223.1
for air supply duct sizes and
restrictions.

c)

Equipment located in ventilated spaces; all air from out-
doors.
Refer to the latest edition of the "National Fuel Gas
Code" ANSI Z223.1
for air supply duct sizes and
restrictions.

d) Equipment located in ventilated spaces; all air from out-

doors through ventilated attic.
Refer to the latest edition of the "National Fuel Gas
Code" ANSI Z223.1
for air supply duct sizes and
restrictions.

Note: Ensure sufficient ventilation air to prevent elevat-
ed temperatures in closets and ventilated spaces.
When an exhaust fan is installed in the same room as the
water heater, the supply air openings must be of sufficient
capacity to prevent a backflow of air through the water
heater exhaust venting.

Burn Hazard

Do not touch vent.
Doing so can result in
burns.

– 10 –

VENTILATED

SPACE

PERMANENT
OPENINGS

EQUIPMENT LOCATED IN VENTILATED

SPACES; ALL AIR FROM INSIDE THE BUILDING.

(a)

UNCONFINED
SPACE

VENTILATED

SPACE

ATTIC LOUVERS TO OUTDOORS

EQUIPMENT LOCATED IN VENTILATED SPACES; ALL

AIR FROM OUTDOORS THROUGH VENTILATED ATTIC.

(d)

INLET AIR
DUCT

OUTLET

AIR

BASEMENT INSTALLATION, EQUIPMENT LOCATED

IN VENTILATED SPACES; ALL AIR FROM OUTDOORS

(b)

VENTILATED

SPACE

GRADE

300mm

(12 in.)

300mm

(12 in.)

Figure 5

Combustion Air Supply Openings And Ducts
(U.S.A.)

COMBUSTION

AIR DUCT

PERMANENT

VENTILATION

AIR.

300mm

(12 in.)

ABOVE

GRADE

OR

SNOW

LINE

EQUIPMENT LOCATED IN VENTILATED

SPACES; ALL AIR FROM OUTDOORS.

(c)

VENTILATED

SPACE

COMBUSTION

300mm (12 in.)

300mm (12 in.)

300mm (12 in.)

OUTDOORS

AIR DUCT

VENTILATION