Roduct, Pecifications, Pcb090-5 (si u – Goodman Mfg SS-PCB50 User Manual

Page 8: Pcb090-5 (e, Erformance, Cont, Ooling, Apacity, Omponent, Ressure

background image

8

SS-PCB50

P

RODUCT

S

PECIFICATIONS

INDOOR

AIR

CONDENSER AIR TEMPERATURE

75°F

85°F

95°F

105°F

115°F

SCFM

WB

Total

Kbtuh

Sens

Kbtuh

Kw

Total

Kbtuh

Sens

Kbtuh

Kw

Total

Kbtuh

Sens

Kbtuh

Kw

Total

Kbtuh

Sens

Kbtuh

Kw

Total

Kbtuh

Sens

Kbtuh

Kw

2550

72

111.8

52.8

8.36

104.6

49.6

9.29

97.5

46.3

10.23

90.3

43.0

11.17

83.1

39.7

12.10

67

103.2

63.8

7.82

96.1

61.1

8.73

89.1

58.4

9.64

82.1

55.6

10.55

75.0

52.9

11.46

62

93.9

78.5

7.46

89.0

74.1

8.30

84.0

69.8

9.14

79.1

65.5

9.98

74.1

61.1

10.82

57

90.7

85.2

7.18

85.2

79.1

8.06

79.8

73.1

8.94

74.3

67.1

9.83

68.8

61.1

10.71

3000

72

116.6

58.5

8.63

108.9

55.1

9.58

101.2

51.7

10.53

93.5

48.2

11.48

85.7

44.8

12.43

67

107.0

74.9

8.08

99.9

71.0

9.01

92.8

67.1

9.93

85.7

63.2

10.86

78.6

59.3

11.78

62

97.6

91.6

7.53

92.0

85.4

8.49

86.3

79.2

9.44

80.7

73.0

10.40

75.0

66.8

11.35

57

97.6

91.6

7.53

92.0

85.4

8.49

86.3

79.2

9.44

80.7

73.0

10.40

75.0

66.8

11.35

3450

72

119.5

62.9

8.82

111.7

59.6

9.77

103.9

56.3

10.73

96.2

53.0

11.69

88.4

49.8

12.64

67

109.9

84.2

8.28

102.7

79.7

9.21

95.6

75.2

10.14

88.4

70.7

11.07

81.3

66.2

11.99

62

103.2

97.2

7.89

97.0

90.6

8.86

90.9

83.9

9.84

84.7

77.3

10.81

78.6

70.7

11.78

57

103.2

97.2

7.89

97.0

90.6

8.86

90.9

83.9

9.84

84.7

77.3

10.81

78.6

70.7

11.78

F

AN

P

ERFORMANCE

D

ATA

(

CONT

.)

C

OMPONENT

P

RESSURE

D

ROPS

MODEL

CFM

WET COIL

ELEC. HEAT

MED. EFF. FILTERS

ECONO. RETURN AIR DAMP-

ER

090

2600

0.06

0.03

0.03

0.14

3000

0.06

0.04

0.04

0.14

3400

0.07

0.05

0.05

0.18

120

3600

0.05

0.05

0.03

0.14

4000

0.05

0.06

0.04

0.14

4400

0.05

0.08

0.04

0.14

180

5000

0.13

0.10

0.06

0.18

5400

0.13

0.12

0.06

0.21

5600

0.16

0.13

0.08

0.23

C

OOLING

C

APACITY

D

ATA

PCB090-5 (SI U

NITS

)

INDOOR

AIR

CONDENSER AIR TEMPERATURE

23.9°C

29.4°C

35.0°C

40.6°C

46.1°C

L/S

WB

Total

Cap.

Sens
Cap.

Kw

Total

Cap.

Sens
Cap.

Kw

Total

Cap.

Sens
Cap.

Kw

Total

Cap.

Sens
Cap.

Kw

Total

Cap.

Sens
Cap.

Kw

1203

22.2

32.77

15.48

8.36

30.67

14.52

9.29

28.56

13.56

10.23

26.46

12.60

11.17

24.35

11.64

12.10

19.4

30.23

18.70

7.82

28.17

17.90

8.73

26.11

17.10

9.64

24.05

16.31

10.55

21.99

15.51

11.46

16.7

27.52

23.00

7.46

26.07

21.73

8.30

24.62

20.45

9.14

23.17

19.18

9.98

21.72

17.91

10.82

13.9

26.59

24.96

7.18

24.98

23.20

8.06

23.38

21.43

8.94

21.77

19.67

9.83

20.17

17.91

10.71

1416

22.2

34.17

17.16

8.63

31.91

16.15

9.58

29.65

15.14

10.53

27.39

14.14

11.48

25.13

13.13

12.43

19.4

31.36

21.95

8.08

29.28

20.81

9.01

27.20

19.66

9.93

25.12

18.52

10.86

23.03

17.38

11.78

16.7

28.62

26.83

7.53

26.96

25.02

8.49

25.30

23.20

9.44

23.65

21.39

10.40

21.99

19.58

11.35

13.9

28.62

26.83

7.53

26.96

25.02

8.49

25.30

23.20

9.44

23.65

21.39

10.40

21.99

19.58

11.35

1628

22.2

35.01

18.42

8.82

32.73

17.46

9.77

30.46

16.50

10.73

28.18

15.54

11.69

25.90

14.59

12.64

19.4

32.19

24.67

8.28

30.10

23.35

9.21

28.00

22.04

10.14

25.91

20.72

11.07

23.81

19.40

11.99

16.7

30.24

28.49

7.89

28.44

26.54

8.86

26.64

24.60

9.84

24.84

22.65

10.81

23.03

20.71

11.78

13.9

30.24

28.49

7.89

28.44

26.54

8.86

26.64

24.60

9.84

24.84

22.65

10.81

23.03

20.71

11.78

Sensible heat capacities shown are based on 26.7°C DB entering air at the evaporator coil. For sensible heat capacities at other
than 26.7°C DB, deduct 44.32 W per 47 L/S of evaporator coil air for each degree below 26.7°C, or add 44.32 W per 47 L/S of
evaporator coil air per degree above 26.7°C.

PCB090-5 (E

NGLISH

U

NITS

)

Sensible heat capacities shown are based on 80°F DB entering air at the evaporator coil. For sensible heat capacities at other
than 80°F DB, deduct 84 BTU/h per 100 CFM of evaporator coil air for each degree below 80°F, or add 84 BTU/h per 100 CFM of
evaporator coil air per degree above 80°F.