Roduct, Pecifications, Pcb180-5 (e – Goodman Mfg SS-PCB50 User Manual

Page 10: Ooling, Apacity, Cont, Nglish, Nits, Vaporator, Otor

background image

10

SS-PCB50

P

RODUCT

S

PECIFICATIONS

INDOOR

AIR

CONDENSER AIR TEMPERATURE

75°F

85°F

95°F

105°F

115°F

SCFM WB

Total

Kbtuh

Sens

Kbtuh

Kw

Total

Kbtuh

Sens

Kbtuh

Kw

Total

Kbtuh

Sens

Kbtuh

Kw

Total

Kbtuh

Sens

Kbtuh

Kw

Total

Kbtuh

Sens

Kbtuh

Kw

4760

72

219.0

100.8

16.42

205.3

95.6

18.63

191.7

90.4

20.83

178.0

85.1

23.04

164.4

79.9

25.25

67

202.0

121.4

15.36

188.6

117.7

17.50

175.2

113.9

19.63

161.8

110.2

21.76

148.4

106.5

23.89

62

183.8

149.6

14.67

174.5

142.9

16.64

165.2

136.3

18.61

155.9

129.6

20.59

146.6

123.0

22.56

57

177.6

162.6

14.10

167.2

152.7

16.15

156.9

142.8

18.21

146.5

132.9

20.27

136.1

123.0

22.33

5600

72

228.3

111.6

16.97

213.6

106.3

19.21

199.0

100.9

21.45

184.3

95.5

23.68

169.6

90.1

25.92

67

209.5

142.7

15.87

196.0

136.9

18.05

182.5

131.0

20.22

169.0

125.2

22.40

155.5

119.3

24.46

62

191.1

174.8

14.77

180.5

164.7

17.00

169.8

154.6

19.23

159.1

144.5

21.46

148.4

134.4

23.68

57

191.1

174.8

14.77

180.5

164.7

17.00

169.8

154.6

19.23

159.1

144.5

21.46

148.4

134.4

23.68

6440

72

233.9

119.7

17.33

219.1

114.8

19.59

204.4

109.9

21.85

189.6

105.0

24.11

174.9

100.1

26.37

67

215.1

160.4

16.27

201.5

153.6

18.46

187.9

146.8

20.64

174.3

140.0

22.83

160.7

133.2

25.01

62

202.0

185.6

15.49

190.4

174.7

17.76

178.8

163.9

20.03

167.1

153.0

22.30

155.5

142.1

24.57

57

202.0

185.6

15.49

190.4

174.7

17.76

178.8

163.9

20.03

167.1

153.0

22.30

155.5

142.1

24.57

C

OOLING

C

APACITY

D

ATA

(

CONT

.)

PCB180-5 (E

NGLISH

U

NITS

)

Horsepower/(kW)

BTU/h (KW)

2 (1.49)

4400 (1.29)

3 (2.24)

6200 (1.82)

5 (3.73)

10,500 (3.08)

Sensible heat capacities shown are based on 80 °F DB entering air at the evaporator coil. For sensible heat capacities at other
than 80 °F DB, deduct 84 BTU/h per 100 CFM of evaporator coil air for each degree below 80 °F, or add 84 BTU/h per 100 CFM of
evaporator coil air per degree above 80 °F.

E

VAPORATOR

M

OTOR

H

EAT