Product specifications, Pecifications – Goodman Mfg 13 SEER GPC13M User Manual
Page 3
2
www.goodmanmfg.com
SS-GPC13M
SS-GPC13M
www.goodmanmfg.com
3
P
roduct
S
PecificationS
P
roduct
S
PecificationS
s
PeCifiCations
GPC13
36M41A*
GPC13
36M41C*
GPC13
48M41A*
GPC13
48M41C*
GPC13
60M41A*
GPC13
60M41C*
Cooling Capacity
Total BTU/h
35,000
35,000
45,500
45,500
56,000
56,000
Sensible BTU/h
26,250
25,550
35,945
36,855
40,880
42,560
SEER / EER
13 / 10.9
13 / 11.0
13 / 11.0
13 / 11
13 / 10.9
13 / 10.9
Decibels
80.1
80.1
81.7
81.7
80.2
80.2
AHRI Numbers
4385071
5696964
4385074
5696965
4385077
5696966
Evaporator Motor
Type
DD
DD
EEM
EEM
EEM
EEM
Nominal Cooling CFM
1,080
1,180
1,700
1,675
1,750
1,750
Wheel (DxW)
10 x 9
10 x 9
10 x 9
10 x 9
10 x 9
10 x 9
No. of Speeds
3
3
5
5
5
5
Horsepower - RPM
⅓
⅓
¾
¾
1.0
1.0
Evaporator Coil
Face Area (ft²)
4.52
4.55
6.17
6.20
6.17
6.20
Rows Deep/ Fin per Inch
4/ 14
4/ 14
4/ 14
4/ 14
4/ 14
4/ 14
Drain Size (NPT)
¾"
¾"
¾"
¾"
¾"
¾"
Refrigerant Charge (oz.)
85
70
120
116
195
195
Condenser Fan / Coil
Horsepower - RPM
¼ - 1,075
¼ - 1,075
¼ - 1,075
¼ - 1,075
¼ - 1,075
¼ - 1,075
Fan Diameter / # Fan Blades
22 / 3
22 / 3
22 / 3
22 / 3
22 / 3
22 / 3
Face Area (ft²)
12.29
8.77
15.36
15.36
21.04
21.04
Rows Deep/ Fins per Inch
1/ 24
2/ 27
1/ 24
1/ 24
2/ 16
2/ 16
Compressor
Quantity
1
1
1
1
1
1
Type
Scroll
Scroll
Scroll
Scroll
Scroll
Scroll
Stage
Single
Single
Single
Single
Single
Single
Electrical Data
Voltage-Phase
208/230-1
208/230-1
208/230-1
208/230-1
208/230-1
208/230-1
Compressor RLA/LRA
16.7 / 79
16.7 / 79
19.9 / 109
19.9 / 109
26.4 / 134
26.4 / 134
Indoor Blower FLA / LRA
3.06 / 4.1
3.06 / 4.1
5.8 / -
5.8 / -
7.6 / -
7.6 / -
Outdoor Fan FLA / LRA
1.4 / 2.9
1.4 / 2.9
1.4 / 2.9
1.4 / 2.9
1.4 / 2.9
1.4 / 2.9
Total Unit Amps
21.2
21.2
27.1
27.1
35.4
35.4
Min. Circuit Ampacity¹
25.3
25.3
32.1
32.1
42
42
Max. Overcurrent Protection²
40 amps
40 amps
50 amps
50 amps
60 amps
60 amps
Ship Weight (lbs)
410
365
510
435
533
458
¹ Wire size should be determined in accordance with National Electrical Codes. Extensive wire runs will require larger wire sizes.
² May use fuses or HACR-type circuit breakers of the same size as noted.
Note: Always check the S&R plate for electrical data on the unit being installed.