Heat kit electrical data, Lectrical, Lower – Goodman Mfg 13 SEER GPC13M User Manual
Page 18

18
www.goodmanmfg.com
SS-GPC13M
SS-GPC13M
www.goodmanmfg.com
19
P
roduct
S
PecificationS
P
roduct
S
PecificationS
h
eat
k
it
e
leCtriCal
d
ata
(B
lower
o
nly
, h
eat
M
ode
)
Model and
Heat Kit Usage
Circuit #1
Circuit #2
Single-Point Kit
Actual kW /
BTU@ 240V
MCA¹
MOP²
MCA¹
MOP²
MCA¹
MOP²
GPC1336M41**
1.9
---
---
---
--
--
---
HKR-05*, HKR-05C*
21 / 25
25 / 25
---
---
25
40
4.75 / 16,200
HKR-08*, HKR-08C*
32 / 36
35 / 40
---
---
34 / 39
40 / 40
7.0 / 23,800
HKR-10*, HKR-10C*
43 / 49
45 / 50
---
---
45 / 52
60 / 60
9.5 / 32,400
HKP-15C*
43 / 49
45 / 50
21 / 25
25 / 25
66 / 76
70 / 80
14.25 / 48,600
GPC1348M41**
7.3
---
---
---
--
--
---
HKR-05*, HKR-05C*
21 / 25
25 / 25
---
---
32
50
4.75 / 16,200
HKR-08*, HKR-08C*
32 / 36
35 / 40
---
---
38 / 40
50
7.0 / 23,800
HKR-10*, HKR-10C*
43 / 49
45 / 50
---
---
49 / 56
60 / 60
9.5 / 32,400
HKP-15C*
43 / 49
45 / 50
21 / 25
25 / 25
70 / 80
80 / 90
14.25 / 48,600
HKP-20C
43 / 49
45 / 50
43 / 49
45 / 50
92 / 105
100 / 110
19.0 / 64,800
GPC1360M41**
9.5
---
---
---
--
--
---
HKR-05*, HKR-05C*
21 / 25
25 / 25
---
---
42
60
4.75 / 16,200
HKR-08*, HKR-08C*
32 / 36
35 / 40
---
---
42
60
7.0 / 23,800
HKR-10*, HKR-10C*
43 / 49
45 / 50
---
---
51 / 58
60 / 60
9.5 / 32,400
HKP-15C*
43 / 49
45 / 50
21 / 25
25 / 25
72 / 82
80 / 90
14.25 / 48,600
HKP-20C
43 / 49
45 / 50
43 / 49
45 / 50
93 / 107
100 / 110
19.0 / 64,800
¹ Minimum Circuit Ampacity @ 208 / 240 V
² Maximum Overcurrent Protection Device @ 208 / 240 V
* Revision level that may or may not be designated
C Circuit breaker option
^ Heat Kit requires three-phase power supply
Note: HKP-15C* and HKP-20C* replace HKR-15C and HKR-20C respectively to meet new UL1995 requirements.