Airflow data, Irflow, Roduct – Goodman Mfg 13 SEER GPC13M User Manual
Page 16: Pecifications

16
www.goodmanmfg.com
SS-GPC13M
SS-GPC13M
www.goodmanmfg.com
17
P
roduct
S
PecificationS
P
roduct
S
PecificationS
a
irflow
d
ata
Model
Motor
Tap Speed
Volts
E.S.P (In. of H
2
O)
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
GPC13
36M41**
Low
230
CFM
1,122
1,078
1,032
972
915
804
687
558
Watts
338
330
321
310
300
283
264
250
Med
230
CFM
1,387
1,331
1,264
1,209
1,119
1,041
935
748
Watts
456
440
428
412
399
382
363
330
High
230
CFM
1,521
1,454
1,388
1,311
1,230
1,144
1,055
939
Watts
534
521
510
490
477
461
442
420
GPC13
36M41C*
Low
230
CFM
1,122
1,078
1,032
972
915
804
687
558
Watts
338
330
321
310
300
283
264
250
Med
230
CFM
1,387
1,331
1,264
1,209
1,119
1,041
935
748
Watts
456
440
428
412
399
382
363
330
High
230
CFM
1,521
1,454
1,388
1,311
1,230
1,144
1,055
939
Watts
534
521
510
490
477
461
442
420
GPC13
48M41A*
T1
230
CFM
1,440
1,395
1,360
1,310
1,265
1,235
1,190
1,130
Watts
275
285
295
315
325
335
345
355
T2 / T3
230
CFM
1,795
1,765
1,715
1,695
1,650
1,600
1,500
1,375
Watts
475
490
505
520
530
535
510
475
T4 / T5
230
CFM
1,860
1,820
1,785
1,745
1,700
1,625
1,515
1,395
Watts
515
530
545
565
570
550
535
485
GPC13
48M41C*
T1
230
CFM
1,451
1,404
1,356
1,309
1,262
1,215
1,168
1,121
Watts
255
264
273
282
291
299
308
317
T2 / T3
230
CFM
1,809
1,762
1,715
1,667
1,620
1,573
1,526
1,479
Watts
444
453
462
471
479
488
497
506
T4 / T5
230
CFM
1,885
1,838
1,790
1,743
1,696
1,649
1,602
1,555
Watts
484
493
502
510
519
528
537
546
GPC13
60M41A*
T1
230
CFM
1,755
1,720
1,685
1,645
1,615
1,570
1,530
1,465
Watts
420
435
455
460
475
490
500
500
T2 / T3
230
CFM
1,850
1,820
1,775
1,735
1,705
1,675
1,610
1,495
Watts
480
500
515
525
535
555
545
520
T4 / T5
230
CFM
2,180
2,125
2,050
1,975
1,875
1,800
1,655
1,530
Watts
770
755
725
700
675
640
575
540
GPC13
60M41C*
T1
230
CFM
1,774
1,731
1,688
1,645
1,602
1,559
1,515
1,472
Watts
444
453
463
473
483
493
503
512
T2 / T3
230
CFM
1,891
1,848
1,804
1,761
1,718
1,675
1,632
1,589
Watts
515
525
535
544
554
564
574
584
T4 / T5
230
CFM
2,105
2,062
2,018
1,975
1,932
1,889
1,846
1,803
Watts
646
656
666
676
686
696
705
715
Notes
• Data shown is dry coil. Wet coil pressure drop is approximately 0.1” H₂O, for two-row indoor coil; 0.2” H₂O, for three-row indoor coil; and 0.3” H₂O, for
four-row indoor coil.
• Data shown does not include filter pressure drop, approx. 0.08” H₂O.
• ALL MODELS SHOULD RUN NO LESS THAN 350 CFM/TON. USE HIGHER SPEED TAP OR NEXT SIZE LARGER BLOWER ASM. See Repair Parts list.
• Reduce airflow by 2% for 208-volt operation.