beautypg.com

12 servicing, 13 fault finding – Glow-worm EnergySaver 40 User Manual

Page 26

background image

26

221834B

13.1 Electrical

Important. On completion of the Service/Fault Finding task
which has required the breaking and remaking of the electrical
connections the earth continuity, polarity, short circuit and
resistance to earth checks must be repeated using a suitable
multimeter.

Refer to Fault Finding, Wiring, diagram 13.2 and Functional
Flow diagram 13.3.

Note. Failure of an indicator light does not warrant the
replacement of an otherwise satisfactory part.

13.2 Electrical Supply Failure

Failure of the electrical supply will cause the burner to go out.

Operation will normally resume on restoration of the electrical
supply. If the boiler does not relight after an electrical supply
failure the overheat device may need resetting.

To reset, press the reset button on the underside of the boiler,
see diagram 13.4.

If the cutoff operates at any other time press the reset button
and the burner should relight. If the fault persists refer to Fault
Finding Chart.

There is a further cutoff mounted on the flue hood, see diagram
13.5 which also may need resetting.

13.3 Condensate Sensor

Refer to fault finding chart.

The boiler is fitted with a safety device to prevent the boiler from
working if the condensate pipe gets blocked.

Remove the condensate drain cap, diagram 14.2.

If condensate is backing up to the sensor, the drain is blocked
and it must be cleared before the boiler will work. Inspect
external condensate pipe and clear away any debris or ice.

Release ice blockage by using warm cloths on the pipe.

Diagram 12.9

Diagram 12.8

SECURING
SCREW (2)

SILICONE
SLEEVING

IGNITION
AND
SENSING LEAD

SPARK
ELECTRODE

SPARK GAP
3mm to 4mm

GASKET

SECURING
SCREW (3)

CONDENSE
DRAIN TRAP

CAP

WASTE
OUTLET

4060

4061

12 Servicing

Diagram 12.7

INJECTOR
MANIFOLD

SECURING
SCREW (3)

SECURING
SCREW (2)

4059

13 Fault Finding