PRE-INSTALLATION CHECKS
2.2 Extractor fans or cooker hoods must not be placed in the
same room or space as this can cause the appliance to emit
fumes into the room.
2.3 If any of these checks reveal problems do not proceed
with the fitting of the appliance until they have been
rectified.
2. ADDITIONAL VENTILATION
2.1 Additional ventilation is required to comply with the
requirements of the Building Regulations. This must be
provided using a permanently open air vent, of the size
listed, which is positioned so that it is not liable to be
blocked both inside and outside the building.
Model
Stockton 7 Inset Convector - Model: 7125
Stockton 8 Inset Convector - Model: 7126
Stockton
8
Stockton
7
Additional Ventilation
1100
1650
mm2
cm2
in2
11
1.7
16.5
2.56