beautypg.com

13 the battery, Danger – Generac Power Systems 005240 User Manual

Page 13

background image

11

Figure 1.10 – Battery Cable Connections

NOTE:

In areas where temperatures regularly fall below
10° F (-12° C) it is recommended that a pad type
battery heater be installed to aid in cold climate
starting (see Specifications).

NOTE:

The generator is equipped with a battery trickle
charger that is active when the unit is set up for
automatic operation. With the battery installed
and utility power source voltage available to the
transfer switch, the battery receives a trickle
charge while the engine is not running, to prevent
self-discharge. The trickle charger is designed to
help extend the life of the battery by maintain-
ing the battery when the unit is not running. The
trickle charge feature cannot be used to recharge
a discharged battery.

1.13 THE BATTERY

DANGER

Do not dispose of the battery in a fire. The

battery is capable of exploding.

A battery presents a risk of electrical shock

and high short circuit current. The following pre-
cautions are to be observed when working on
batteries:

• Remove the 15A fuse from the generator control

panel.

• Remove watches, rings or other metal objects;
• Use tools with insulated handles;
• Wear rubber gloves and boots;
• Do not lay tools or metal parts on top of the

battery; and

• Disconnect charging source prior to connecting or

disconnecting battery terminals.

Do not open or mutilate the battery. Released

electrolyte has been known to be harmful to the
skin and eyes, and to be toxic.

The electrolyte is a dilute sulfuric acid that is

harmful to the skin and eyes. It is electrically
conductive and corrosive.

The following procedures are to be observed:
• Wear full eye protection and protective clothing;
• Where electrolyte contacts the skin, wash it off

immediately with water;

• Where electrolyte contacts the eyes, flush thor-

oughly and immediately with water and seek
medical attention; and

• Spilled electrolyte is to be washed down with an

acid neutralizing agent. A common practice is to
use a solution of 1 pound (500 grams) bicarbonate
of soda to 1 gallon (4 liters) of water. The bicar-
bonate of soda solution is to be added until the
evidence of reaction (foaming) has ceased. The
resulting liquid is to be flushed with water and the
area dried.

Lead-acid batteries present a risk of fire because

they generate hydrogen gas. The following
procedures are to be followed:

• DO NOT SMOKE when near the battery;
• DO NOT cause flame or spark in battery area; and
• Discharge static electricity from body before touch-

ing the battery by first touching a grounded metal
surface.

Be sure the AUTO/OFF/MANUAL switch is set to

the OFF position before connecting the battery
cables. If the switch is set to AUTO or MANUAL,
the generator can crank and start as soon as the
battery cables are connected.

Be sure the utility power supply is turned off

and the 15A fuse is removed from the generator
control panel, or sparking may occur at the bat-
tery posts as the cables are attached and cause
an explosion.

Servicing of the battery is to be performed or super-
vised by personnel knowledgeable of batteries and
the required precautions. Keep unauthorized person-
nel away from batteries.

See the Specifications section for the correct size
and rating when replacing the battery. When using a
maintenance-free battery, it is not necessary to check
the specific gravity or electrolyte level. Have these
procedures performed at the intervals specified in
the “Service Schedule.” A negative ground system is
used. Battery connections are shown on the wiring
diagrams. Make sure the battery is correctly connect-
ed and terminals are tight. Observe battery polarity
when connecting the battery to the generator set.

Section 1 — General Information

Air-cooled Generators

This manual is related to the following products: