For proper unit performance and maximum operating liferefer to the minimum installation clearances below.

Figure 2

Figure 1

12"

24"

60"

K

A

P

V

K

A

P

V

K

A

P

V

POLE

FENCE

MAJOR OBSTRUCTION

BUILDING

OUTDOOR
CONDENSING

UNIT

72"

24"

SHRUB

A

B

60"

60"

60"

60"

LARGER RECESS OK. IF A> 5xB

12"

6"

60"

60"

60"

6"

60"

60"

6"

60"

60"

SMALL RECESS OK

VERT-I-PAK

®

units must be installed on an outside wall. Confined spaces and/or covered areas should be

avoided. Units should be installed no closer than 12" apart when two units are side by side. If three or more
units are to operate next to one another allow a minimum of 60" between units or pairs of units. Also, a vertical
clearance of 60" should be maintained between units. Units installed on the bottom floor should be mounted at
least 6" off of the ground.

Any time obstructions are present use the
following guidelines for proper spacing
from the VERT-I-PAK louver:

For minor obstructions such as lamp
poles or small shrubbery a clearance
of 24” from the outdoor louver should
be maintained.

For major obstructions such as a solid
fence, wall or other heat rejecting
device like a condensing unit, a
minimum distance of 72” should be
kept.

®

The above suggestions are for reference only and do not represent all posible installations. Please contact Friedrich for informa-
tion regarding affects of other installation arrangements.

By following these simple recommendations you can be confident that your Friedrich Vert-I-Pak will provide years of worry-free
operation.