Electrical Data

Turn OFF electric power before service or
installation.

Unit must be properly grounded.

Unit must have correct fuse or circuit breaker
protection.

Unit’s supply circuit must have the correct
wire conductor size.

All electrical connections and wiring must be
installed by a qualified electrician and
conform to the National Electrical Code and all
local codes which have jurisdiction.

Failure to do so can result in property
damage, personal injury and /or death.

Electrical Requirements

Wire Size

Sample Nameplate

120524

COOLING EQUIPMENT

FOLLOWING ITEMS

OUTDOOR GRILLE

INDOOR GRILLE

SA

MP

LE

Electrical Rating Tables

Use ONLY wire size recommended for
single outlet branch circuit.

Use ONLY type and size fuse or HACR
circuit breaker indicated on unit’s rating
plate (See sample below). Proper over
current protection to the units is the respon-
sibility of the owner.

Unit MUST be grounded from branch circuit
to unit, or through separate ground wire
provided on permanently connected units.
Be sure that branch circuit or general
purpose outlet is grounded.

Use recommended wire size given in tables
and install a single branch circuit. All wiring
must comply with local and national codes.
NOTE: Use copper conductors only.

NOTE: All field wiring must comply with NEC and local
codes. It is the responsibility of the installer to insure that
the electrical codes are met.

NOTE: Use copper conductors ONLY. Wire sizes are per
NEC. Check local codes for overseas applications.

AWG --- American Wire Gauge
* Single circuit from main box.
** Based on 100’ or less of copper, single insulated con-

ductor at 60° C

Electrical shock hazard.

WARNING

Nameplate Maximum Circuit

Breaker Size

AWG Wire Size

25A

10

30A

10

45A

6

60A

4

Recommended branch circuit wire sizes