4.2.

Client Side Connection Descriptors

Section Title

Connections

Column Title

Function

Legal Values

Port

Specify which port the device is
connected to the FieldServer

P1-P8, R1-R2

1

Protocol

Specify protocol used

Setra370

Baud*

Specify baud rate

110 – 115200, standard baud
rates only, 2400.

Parity*

Specify parity

Even, Odd, None, Mark, Space

Data_Bits*

Specify data bits

7, 8

Stop_Bits*

Specify stop bits

1

Handshaking*

Specify hardware handshaking

The Setra Model 370 does not support
handshaking.

RTS, RTS/CTS, None

Poll _Delay*

Time between internal polls

0-32000 seconds, 1 second

Example

// Client Side Connections

Connections
Port,

Protocol,

Baud, Parity,

Handshaking,

Poll_Delay

P8,

Setra370,

2400,

None,

None,

0.100s

4.3.

Client Side Node Descriptors

Section Title

Nodes

Column Title

Function

Legal Values

Node_Name

Provide name for node

Up to 32 alphanumeric
characters

Node_ID

This commonly used parameter has no meaning for this driver and may be
omitted.

Protocol

Specify protocol used

Setra370.

Connection

Specify which port the device is connected
to the FieldServer

P1-P8, R1-R2

1

Example

// Client Side Nodes

Nodes

Node_Name,

Protocol,

Connection

Gage1,

Setra370,

P8

1

Not all ports shown are necessarily supported by the hardware. Consult the appropriate Instruction