5.

Configuring the FieldServer as a Setra Model 370 Digital Pressure Gage

Server

For a detailed discussion on FieldServer configuration, please refer to the FieldServer
Configuration Manual. The information that follows describes how to expand upon the factory
defaults provided in the configuration files included with the FieldServer.

This section documents and describes the parameters necessary for configuring the FieldServer
to communicate with a Setra Model 370 Digital Pressure Gage Client

The configuration file tells the FieldServer about its interfaces, and the routing of data required.
In order to enable the FieldServer for Setra Model 370 Digital Pressure Gage communications,
the driver independent FieldServer buffers need to be declared in the “Data Arrays” section, the
FieldServer virtual node(s) needs to be declared in the “Server Side Nodes” section, and the
data to be provided to the Clients needs to be mapped in the “Server Side Map Descriptors”
section. Details on how to do this can be found below.

Note that in the tables, * indicates an optional parameter, with the bold legal value being the
default.

5.1.

Server Side Connection Descriptors

Section Title

Connections

Column Title

Function

Legal Values

Port

Specify which port the device is
connected to the FieldServer

P1-P8, R1-R2

2

Protocol

Specify protocol used

Setra370

Baud*

Specify baud rate

110 – 115200, standard
baud rates only

Parity* Specify

parity

Even, Odd, None, Mark,
Space

Data_Bits*

Specify data bits

7, 8

Stop_Bits*

Specify stop bits

1

Handshaking*

Specify hardware handshaking

RTS, RTS/CTS, None

Server_Hold_Timeout*

Specifies time FieldServer will
reserve Server side connection
while waiting for the Client side to
update data in Data_Array (if
necessary)

>1.0s


Example

// Server Side Connections

Connections
Port,

Protocol,

Baud,

Parity,

Handshaking,

P8,

Setra370,

9600,

None,

None,

2

Not all ports shown are necessarily supported by the hardware. Consult the appropriate Instruction

manual for details of the ports available on specific hardware.