This appliance may be vented through a

manufactured chimney system or a masonry

chimney using a B-vent adapter or a chim-

ney liner system if all are listed, inspected

and approved by local codes and/or building

authorities.
The examples shown in Figure 9 are typi-

cal of most B-vent installations and codes

practices.
Example 1: Shows the minimum allowable

system height and lateral offset for a 60° or

greater inclination. Code specifies that offsets

at 60° or greater are considered horizontal

and must follow the 75% rule for lateral to

total vertical system height. Codes also al-

lows only one offset in the total system when

at 60° or greater. The total vertical height in

this example represents the minimum height

of 8 feet and therefore the allowable lateral

is 6 feet when the 75% rule applies. If the

lateral length must exceed 75% then the

system must be sized in accordance with the

Category I venting tables.
Example 2: Shows a multiple offset each at

45° of inclination. Multiple offsets are permit-

ted if they do not exceed 45° of inclination. The

total lengths of the two offsets are not required

to meet the 75% allowable rule.
Example 3: Shows a single offset at 45° of

inclination and therefore the lateral length at

10 feet of offset does not have to meet the

75% rule.

Maintain

Listed

Clearance

Maintain

Listed

Clearance

12' Min.

12' Min.

45°

45°

6'

8'

12' Min.

60°

45°

Position

Firestop

Position

Firestop

Position

Firestop

Listed

Vent Cap

Listed

Vent Cap

Listed

Vent Cap

Maintain

Listed

Clearance

Maintain

Listed

Clearance

Maintain

Listed

Clearance

Maintain

Listed

Clearance

Support Each

Lateral At

Least Every

6 Feet

Maintain

Listed

Clearance

10'

EXAMPLE 3

EXAMPLE 2

EXAMPLE 1

Figure 9 - Typical B-Vent Configuration

VeNtING INstAllAtIoN

Continued

In each case the offsets must be supported

and firestops must be positioned wherever

the vent must pass through a sub-floor, ceil-

ing joist or an attic overhang. The vent pipe

must terminate vertically into a listed type vent

cap and extend a sufficient height through

an approved roof flashing, roof jack or a roof

thimble. At all points the listed clearances

must be maintained.
Vent terminations must be located in ac-

cordance with height and proximity rules of

NFPA No. 54. These rules apply to vents at

12" diameter or less and require a minimum

height in accordance with the roof pitch and a

minimum of 8 feet distance from a vertical wall

or obstruction (see Figure 10, page 10).
If venting horizontally through a side wall be-

comes necessary, a listed thimble approved

for use with B-type vent must be used. Check

with your local codes before venting through

a side wall.
Some codes areas allow the use of existing B-

type vent systems if the system is at or above

the recommended diameter of the flue.
The flue connection must be made using

listed B-type connectors and the existing

system must be code inspected for damage

and proper installation.