UMIDIFIER

A

DJUSTMENT

The TM-2000 must now be adjusted so that it activates after heated air circulation begins, and de-activates before the
heated air circulation ends.

1. Turn the adjustment knob on the Housing Assembly to the lowest sensitivity setting (fully clockwise). Set the Housing

Assembly power switch to the “ON” position. THE TM-2000 SHOULD NOT ACTIVATE AT THIS TIME.

2. Set the furnace thermostat to cause continued operation of the furnace.

3. At approximately 2 minutes after the furnace begins blowing heated air through the ductwork, turn the adjustment

knob counterclockwise just until the TM-2000 activates. This will be indicated by glowing of the “ON” light on the
Housing Assembly.

4. Lower the thermostat to end the furnace heating cycle. Check to be sure the TM-2000 deactivates at least 30 seconds

before the furnace stops blowing air through the ductwork. If the TM-2000 does not deactivate soon enough, turn the
adjustment knob slightly clockwise.

5. Check the operation of the TM-2000 for several more heating cycles to be sure of proper operation as described

above, and adjust the TM-2000 as necessary. If proper operation cannot be obtained, call Field Controls Customer
Service at (252) 522-3031 for further assistance.

6. Once proper adjustment has been made, humidity levels can be increased or decreased by small adjustments of the

TM-2000. Always verify proper operation as described above, after any adjustment has been made.

7. Inspect the system for leaks, loose wires, etc. SEVERAL DROPS OF WATER PER HEATING CYCLE FROM THE

DRAIN TUBE ARE NORMAL. IF SIGNIFICANTLY MORE IS OBSERVED, CALL FIELD CONTROLS CUSTOMER
SERVICE, OR CONSULT THE TROUBLESHOOTING GUIDE IN THIS MANUAL.

W

HEN

H

UMIDIFICATION

I

S

R

EQUIRED

1. Plug the transformer into the receptacle.

2. Open the saddle valve completely.

3. Place the "ON/OFF" switch in the "ON" position.

4. Check for proper sequence of operation by setting thermostat to call for heat and follow through complete cycle.

N

OZZLE

C

APACITY

C

HART

Table 1

NOZZLE

SIZE

PART

NUMBER

GAL/DAY

HEATED

FLOOR
SPACE

STD/OPT

0.65

GPH

46017401

UP TO 9

UP TO

3000

SQ. FT.

STANDARD

1.00

GPH

46017402

UP TO 12

UP TO

4000

SQ. FT.

OPTIONAL

1.35

GPH

46017403

UP TO 18

UP TO

5000

SQ. FT.

OPTIONAL

E

LECTRICAL

R

ATING

Table 2

VOLTS

AMPS

VA

Hz

24 VAC

0.40

10

60