beautypg.com

Model fc200hrv, Performance, Dimensions fc200hrv – Field Controls Heat Recovery Ventilator FC95HRV. User Manual

Page 11

background image

DIMENSIONS FC200HRV

inches (mm)

Model FC200HRV

All units conform to CSA and UL standards.

THERMALLY CONDUCTIVE, PATENTED ALUMINUM CORE

The cross-flow heat recovery core transfers heat between the two

airstreams. It is easily removed for cleaning or service.
MOTORS AND BLOWERS

Each air stream has one centrifugal blower driven by a common PSC

motor. 2 speed fan operation.
FILTERS

Washable air filters in exhaust and supply air streams.
MOUNTING THE HRV

Four threaded inserts at corners of the cabinet designed to accept the “S”

hooks and hanging straps supplied with the unit.
DEFROST

Recirculating damper defrost system.
CASE

Twenty gauge prepainted galvanized steel (G60) for superior corrosion

resistance. Insulated to prevent exterior condensation. Drain connections 2

- 1/2" (12 mm) OD. Balancing ports are located in the door.

WEIGHT

71 lbs. (32.5 kg) SHIPPING WEIGHT 73 lbs (33.5 kg)

ELECTRONICS

• Built-in Relay for Interfacing to furnace

OPTIONAL CONTROLS

# DHVC Ventilation Control

• 2 Speed Fan setting (Low/High) • Dehumidistat

#HHSC Healthy Home System Control

• Automatically activates the unit to deliver fresh air into your home

#DH1

Dehumidistat

• Initiates high speed ventilation when the indoor humidity level exceeds

the set point
OPTIONAL TIMERS

#VTC

Ventilation Timer Control - Initiates high speed ventilation

for 20, 40, or 60 minutes, (3 wire) 20 gauge wire (min.) 100'

length

OPTIONAL ACCESSORIES

#WH 186 Weatherhoods, Two -6” (150 mm) c/w 1/4” (6 mm) mesh

screen

Date: ___________________________________________
Tag: _____________________Qty:___________________
Project: _________________________________________
Engineer: _______________________________________

Contractor: ______________________________________
Supplier: ________________________________________
Quote#: _________________________________________
Submitted by: ____________________________________

*

Sensible Efficiency – thermal **Latent Efficiency – moisture

Note: Effectiveness - based on temp. differential between the 2 airstreams

Efficiency – takes into account all power inputs

Performance

(HVI certified)

Net supply air flow in cfm (L/s) against external static pressure

E.S.P

(external static pressure)

[cfm (L/s)]

@ 0.1" (25 Pa)

207 (97)

@ 0.2" (50 Pa)

200 (94)

@ 0.3" (75 Pa)

184 (87)

@ 0.4" (100 Pa)

171 (80)

@ 0.5" (125 Pa)

152 (71)

@ 0.6" (150 Pa)

130 (61)

@ 0.7" (175 Pa)

116 (55)

@ 0.8" (200 Pa)

86 (40)

Max. Temperature Recovery

74%

Sensible Effectiveness
@ 66 cfm (31 L/s)

32°F (0°C)

74%

*Sensible Efficiency
@ 66 cfm (31 L/s)

32°F (0°C)

64%

*Sensible Efficiency
@ 109 cfm (51 L/s)

-13°F (-25°C)

62%

VAC @ 60HZ

120

WATTS / Low speed.

87

WATTS / High speed

164

Amp rating

1.4

LOW

Hi 1

Hi 2

Hi 3

40

60

80

100

120

140

160

180

200

220

0

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

0.9

Static Pressure (in w.g.)

A

ir

Fl

ow

(c

fm

)

Hi 3 - High Speed
Hi 2 - Medium High Speed
Hi 1 - Medium Speed
Low - Low speed
* Manufacturers Data

WARRANTY

Units carry a LIFETIME warranty on the heat

recovery core and a 5 year replacement parts

warranty.

BALANCING DAMPER

33 5/8"

(850 mm)

STALE AIR

FROM INSIDE

FRESH AIR

FROM OUTSIDE

STALE AIR

TO OUTSIDE

FRESH AIR

TO INSIDE

14 3/4"

(375 mm)

1

9

"

(4

8

3

m

m

)

*All Duct Connections 6" (150 mm)

CONDENSATE DRAINS

FILTERS

BLOWERS

*NOTE: Front
clearance

of 25 inches

(635 mm)
is recommended
for servicing unit.

RECIRCULATING

DEFROST

DAMPER

MOTOR

CORE

BALANCING DAMPER

All Duct Connections 6” (160 mm)

INSTALLER SELECTABLE HIGH SPEED SETTINGS
Adjustable DIP switches are located on the circuit board. Hi3 is

the factory setting. Refer to the Operation and Installation

manual for the adjustment instructions.

11