CF SERIES GAS FRYERS

CHAPTER 2: INSTALLATION INSTRUCTIONS

2-6

2.4 Connection to Gas Line


DANGER

Before connecting new pipe to this appliance, the pipe must be blown out

thoroughly to remove all foreign material. Foreign material in the burner and gas

controls will cause improper and dangerous operation.


DANGER

When pressure-testing incoming gas supply lines, disconnect the fryer from the gas

line if the test pressure will be ½ PSIG (3.45 kPa, 13.84 inches W.C.) or greater to

avoid damage to the fryer’s gas tubes and gas valve(s).


The CF Series fryer has received the CE mark for the countries and gas categories indicated in the
table below.

BE

I2E+(S)

I3P

G20/G25

G31

20/25

37

DE

I2 ELL

13P

G20/G25

G31

20
50

FR

II2Esi3P

G20/G25

G31

20/25

37 ET 50

LU

I2E

G20/G25

20/25

ES

II2H3P

G20
G31

20

37 ET 50

NL

II2L3P

G25
G31

25
50

IE-PT-GB

II2H3P

G20
G31

20
37

CE Approved Gas Categories

Country

Category

Gas

Pressure

(m bar)

DK-GR-IT

I2 H

G20

20



The size of the gas line used for installation is very important. If the line is too small, the gas
pressure at the burner manifold will be low. This may cause slow recovery and delayed ignition.
The incoming gas supply line should be a minimum of 1½" (38 mm) in diameter. Refer to the chart
on the following page for the minimum sizes of connection piping.