2.2 Power
Requirements
Three (3) Phase Requirements
MODEL VOLTAGE
WIRE
SERVICE
MINIMUM WIRE
SIZE
AWG (mm)
AMPS
(per leg)
1814E 14kW
208 3 6
(4.11)
39
1814E 14kW
240 3 6
(4.11)
34
1814E 14kW
480 3 8
(2.59)
17
1814E 14kW
220/380
4 6
(4.11)
21
1814E 14kW
240/415
4 6
(4.11)
20
1814E 14kW
230/400
4 6
(4.11)
21
1814E 17kW
208 3 6
(4.11)
48
1814E 17kW
240 3 6
(4.11)
41
1814E 17kW
480 3 6
(4.11)
21
1814E 17kW
220/380
4 6
(4.11)
26
1814E 17kW
240/415
4 6
(4.11)
24
1814E 17kW
230/400
4 6
(4.11)
25
1814E 22kW
208 3 4
(5.19)
61
1814E 22kW
240 3 4
(5.19)
53
1814E 22kW
480 3 6
(4.11)
27
1814E 22kW
220/380
4 6
(4.11)
34
1814E 22kW
240/415
4 6
(4.11)
31
1814E 22kW
230/400
4 6
(4.11)
32
Single Phase Requirements
MODEL VOLTAGE
WIRE
SERVICE
MINIMUM WIRE
SIZE
AWG (mm)
AMPS
(per leg)
1814E 14kW
208 2 3
(5.83)
68
1814E 14kW
240 2 4
(5.19)
59
1814E 14kW
480 2 8
(3.26)
30
NOTICE
If this appliance is permanently connected to fixed wiring, it must be connected by
means of copper wires having a temperature rating of not less than 167°F (75°C).
DANGER
This appliance must be connected to a power supply having the same voltage and
phase as specified on the rating plate located on the inside of the appliance door.
DANGER
All wiring connections for this appliance must be made in accordance with the
wiring diagram(s) furnished with the appliance. Refer to the wiring diagram(s)
affixed to the inside of the appliance door when installing or servicing this
equipment.
2.3
Positioning the Fryer
DANGER
No structural material on the fryer should be altered or removed to accommodate
placement of the fryer under a hood. Questions? Call the Frymaster Service Hotline
at 1-800-551-8633.