beautypg.com

FieldServer FS-8704-12 User Manual

Page 18

background image

FS-8704-12 GE-EGD Driver Manual

Page 18 of 23

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com

Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: [email protected]

Map_Descriptors
Map_Descriptor_Name

, Data_Array_Name

, Data_Array_Offset

, Function

, Node_Name

, Length

, Ge_producerId

Ge_exchangeId

, Ge_data_type

, Ge_offset

Q1

, DATA_Q

, 0

, Passive

, PLC90-30

, 1

, 1.2.3.4

, 1

, %q

, 0

R1

, DATA_R

, 0

, Passive

, PLC90-30

, 1

, 1.2.3.4

, 1

, %r

, 1

I1

, DATA_R

, 0

, Passive

, PLC90-30

, 2

, 1.2.3.4

, 1

, %u

, 3

R2

, DATA_R

, 1

, Passive

, PLC90-30

, 1

, 1.2.3.4

, 1

, %r

, 5

I2

, DATA_R

, 2

, Passive

, PLC90-30

, 1

, 1.2.3.4

, 1

, %i

, 7

Q2

, DATA_R

, 1

, Passive

, PLC90-30

, 1

, 1.2.3.4

, 1

, %q

, 8


Must correspond to the
‘Local Producer’ in the
EGD configuration. Not
necessarily the IP
address of the producer
port.

These data types must
correspond to the
references in the EGD
range configuration.

These offsets
must correspond
to the offsets in
the EGD
configuration.

Refer to Appendix C.1 to see how many
items are being transmitted. Note that
the %Q, %I references are actually byte
references and not bit references as
they are always produced in multiples
of 8 and are always byte aligned.