beautypg.com

Configuring the fieldserver as a ge-egd server, Server side connection parameters, Server side node parameters – FieldServer FS-8704-12 User Manual

Page 11

background image

FS-8704-12 GE-EGD Driver Manual

Page 11 of 23

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com

Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: [email protected]

6

CONFIGURING THE FIEL DSERVER AS A GE-EGD SERVER

6.1

Server Side Connection Parameters

Section Title
Connections
Column Title Function

Legal Values

Adapter

Adapter Name

N1,N2

Protocol

Specify protocol used ge_egd


Example

Adapters
Adapter

, Protocol

N1

, ge_egd

6.2

Server Side Node Parameters

Section Title
Nodes
Column Title

Function

Legal Values

Node_Name

Provide name for Node

Up

to

32

alphanumeric

characters

IP_Address

The IP address in dot format of the EGD-Device.

Nnn.nnn.nnn.nnn
Where nnn is in the range 0-255.

Protocol

Specify protocol used

ge_egd

Adapter

Specify which adapter connects to the network the EGD-
device is connected to.

N1, N2

3


Example

// Producer(Active Server) Side Nodes

Nodes

Node_Name , IP_Address,

, Adapter , Protocol

node_A

, 192.168.1.102, , N1

, ge_egd




3

Not all ports shown are necessarily supported by the hardware. Consult the appropriate Instruction manual for details of the ports available

on specific hardware.