Yosemite Wood Stove

7004-187F September 1, 2008

R

FLOOR PROTECTION

The floor must be non-combustible material, extending beneath heater and to the front/sides/rear as indicated. The floor must be
non-combustible or otherwise adequately protected from radiant heat given off by the unit and from sparks and falling embers. A
layer of thin brick or ceramic tile over a combustible floor is not sufficient.

In USA installations, it is necessary to install a non-combustible floor protector at least 16 inches in front and 8 inches to both
sides of the fuel loading doors. See *exception below.

In Canada, similar floor protection must be provided 18 inches (450mm) in front and 8 inches (200mm) from the sides and rear of
the stove. See *exception below.

*EXCEPTION: Non-combustible floor protections must extend beneath the flue pipe when installed with horizontal venting and
extend 2 inches (51mm) beyond each side.

Minimum 16"

(406mm) from

fuel loading

door

8"

(200mm)

USA

44-1/2"

(1130mm)

Minimum

36-3/4"

(932mm)

Minimum

Fuel loading doors

Front

Side

8"

(200mm)

Minimum 450mm

(18")

from each

fuel loading door

CANADA

1187mm

(46-3/4")

Minimum

Fuel loading doors

Front

Side

200mm

(8")

1264mm

(49-3/4")

Minimum

200mm

(8")

CANADA

200mm (

8")

200mm

(

8")

450mm

(18")

1187mm
(46-3/4")
Minimum

1010mm

(39-3/4")

Minimum

200mm

(

8")

SIDE FUEL DOOR LOCKED SHUT

BOTH FUEL DOORS ACCESSIBLE

DRAWINGS ARE FOR ILLUSTRATION PURPOSES ONLY AND ARE NOT TO SCALE.

16"

(406mm)

from fuel

loading door

8"

(200mm)

USA

Front Fuel

loading door

33"

(838mm)

Minimum

36-3/4

"

(933mm)

Minimum

10-1/2"

(267mm)

Minimum Hearth Requirements ONLY

See page 6 for stove clearances