beautypg.com

Honeywell PCR-110 User Manual

Page 14

background image

14

Control performance:

Two-step

Display accuracy:

± 0.5 K internal, ±1 digit, at 25 °C

Operating conditions:

0 to 50 °C, 30 to 85 % R.H.,
excluding dew

Storage temperature:

–20 to +80 °C

Data back-up:

Non-volatile memory (EEPROM)

Sensor:

1 PTC

– Sensor cable length:

2.5 m

– Range where cable

–30 °C to +80 °C not fixed

can be used:

–40 °C to +80 °C fixed

– Sensor accuracy:

±2 %

Housing:

PCR-100: L x W x H = 85 x 70 x 61 mm
PCR-110: L x W x H = 70 x 74 x 32 mm

ABS plastic, self-extinguishing
(UL 94 V0)

Protective rating:

Housing: IP 20, Front panel: IP 52
Class of protection 2

Terminals:

10 A screw-type terminal strips,
with wire protection,
tightening torque 0.6 Nm
Max. core cross section 1.5 mm

2

Weight:

PCR-100: Approx. 330 g (inc. sensor).

PCR-110: Approx. 240 g (inc. sensor).

Only operate the unit in dry places.

Errors in the technical data are excepted. We reserve the right to make
changes without prior notice.

This manual is related to the following products: