Honeywell PCR-110 User Manual
Page 10

7.1 Input parameters and input ranges:
Parameter on display
Setting range
(
or
)
(
and
or
)
Preset
E00 Cold store temperature difference
1 to 20 K
2 K
E01 Min. permissible
cold store temp.
–55 °C to E02
–55 °C
E02 Max. permissible
cold store temp.
E01 to +50 °C
+50 °C
E03 Delay time,
relay energizing
0 to 15 mins.
5 mins.
E04 Alarm temperature difference
–50 K to +50 K
20 K
If the set temperature difference E04 is negative, an alarm is given
if it is too cold in the refrigerated area,
e.g. E04 = –10 K, cold store setpoint value = 18°C
➝ alarm at –28 °C in refrigerated area.
If the set temperature difference E04 is positive, the alarm is given
if it is too warm in the refrigerated area,
e.g. E04 = +10 K, cold store setpoint value = –18°C
➝ alarm at –8°C in refrigerated area.
Attention: any change of coldstore set point value changes also the
alarm temperature.
If E04 is set to 0, no alarm will be given.
E05 Alarm delay time
0 to 99 mins.
10 mins.
E06 Sensor calibration T1
–5 to +5 K
0 K
E07 Mode selection
1 = Cooling,
1
2 = Heating
E08 Time between 2 defrost cycles
1 to 24 hours
8 hours
(switch off cooling)
☛ Once the controller has been switched on, defrosting occurs
for the first time at the end of the first time interval.
☛ After defrosting has been initiated manually, the next time
defrosting takes place is after a complete time interval has
elapsed.
10