Quickspecs, P d u f – HP 16A User Manual
Page 6
QuickSpecs
hp Modular Power Distribution Units
(Zero-U/1U Modular PDUs)
DA-11041
World Wide — Version 3 — December 11, 2002
6
M
O D U L A R
P D U F
A M I L Y
I
N F O R M A T I O N
MODEL SELECTION MATRIX
Low Voltage 24A
High Voltage 16A
High Voltage 24A
High Voltage 32A
High Voltage 40A
Part Number
252663-D71
252663-B24
252663-D72
252663-B31
252663-B21
Input Connection
(Single Input)
NEMA L5-30P
Detachable input power
cord with a IEC 320-C20
inlet
Note:
The 16A model with
the detachable cord can be
used only in applications
where the total leakage
current is less than 3.5 mA.
NEMA L6-30P
IEC 309-32A
Field Wired Terminal
Output Connections
(32) NEMA 5-15R
Note: The low volt Extension
Bars w/5-15 outlets should
be used ONLY with the low
volt Control Unit that is
shipped with the low volt
Modular PDU unit.
(16) IEC 320 C-13
Note:
The 16A model ships
with 2 Extension Bars, while
all other 24-40A models ship
with 4 Extension Bars.
(32) IEC 320 C-13
(32) IEC 320 C-13
(24) IEC 320 C-13
(4) IEC 320 C-19
Applications
Connects to low voltage
models of the UPS R3000
XR (and may also be
connected directly into
the facility input)
Connects to the high
voltage models of the
UPS R3000 XR and
R6000
Note:
Except for the UPS
R3000 XR, North America
high volt model, where an
additional cable option kit,
PN 340653-001 (IEC320-
C19 to L6-20P), is needed to
connect a 16A mPDU to the
NA high voltage model of the
UPS R3000 XR
Also connects directly into
the facility input
Note:
You need to purchase
a cable PN 340653-001
(IEC320-C19 to L6-20P) for
North America. Other country
specific cables are managed
at the country level.
Designed to connect
directly into the facility
input
Designed to connect
directly into the facility
input
May be hardwired (
Note:
Hardwiring needs to be done
by a certified on-site
electrician in accordance with
the local electrical installation
codes.)
into the facility
input or to a high voltage
UPS (R12000 XR)