P E C I F I C A T I O N S

Low Voltage 24A

(NA/JPN/LA)

High Voltage 16A

(WW)

High Voltage 24A

(NA/JPN/LA)

High Voltage 32A

(INTL)

High Voltage 40A

(WW)

Part Number

252663-D71

252663-B24

252663-D72

252663-B31

252663-B21

Current (max)

24A

16A

24A

32A

40A

AC Voltage Range

100-127V

200-240V

200-240V

200-240V

200-240V

Frequency (Hertz)

50/60Hz

50/60Hz

50/60Hz

50/60Hz

50/60Hz

Load Capacity (VA)

2880 (@120V)

3680 (@230V)

4992 (@208V)

7360 (@230V

9200 (@230V)

Output Circuit
Breakers

4x15A

2X10A

4x15A

4x15A

4x15A

Overload Protection

Yes

Yes

Yes

Yes

Yes

Indicator Lights

Indicator light on each of the Extension Bars; and a main AC pilot light on the Control Unit

Plugs and Cables
Control Unit
(x1)

Input: 3.6m attached
cable with L5-30P

Output: Four IEC320-
C19 (12A ea)

Input: Detachable
input power cord
(country specific) with
a IEC 320-C20 inlet

Output: Two IEC320-
C19 (8A ea)

Input: 3.6m attached
cable with L6-30P

Output: Four IEC320-
C19 (12A ea)

Input: 3.6m attached
cable with IEC309-32A

Output: Four IEC320-
C19 (12A ea)

Input: Hardwire

Output: Four IEC320-
C19 (12A ea)

Note: Manual ON/Off control provided for each load group; switch guards provided to prevent inadvertent power Off. The Control unit for the 16A model

has 2 outputs while the Control Unit for all other Modular PDUs has 4 outputs. The Extension Bars plug directly into the output-ends of the Control
Unit.

Extension Bars (x4)*

*Except for the 16A
model, which has 2
Extension Bars

Input: 2m attached
cord with IEC320-C20

Output: Each Bar has
8 NEMA 5-15 outlets
(12A max per outlet,
12A max per Bar)

Input: 2m attached
cord with IEC320- C20

Output: Each Bar has
8 C13 outlets
(10A max per outlet,
12A max per Bar)

Input: 2m attached
cord with IEC320- C20

Output: Each Bar has
8 C13 outlets
(10A max per outlet,
12A max per Bar)

Input: 2m attached
cord with IEC320- C20

Output: Each Bar has
8 C13 outlets
(10A max per outlet,
12A max per Bar)

Input: 2m attached
cord with IEC320- C20

Output: 3 Bars each
with 8 C13 (10A max
per outlet, 12A max
per Bar); 1 Bar with 4
C19 (12A max per
outlet, 12A max per
Bar)