BUILDING NETWORK ADAPTER BNA-1C/2CS/2DN

EN1B-0198GE51 R0801

21

For each channel the required termination setting
can be adjusted individually.

At the rear side of the device, a pictogram (Figure
5-2
) symbolizes the different possible bus
terminations.

Figure 5-2

normal

XD505 compatible bus termination for
C- /S- /FS90-Bus connections

It is required to use this switch position
for S-Bus and FS90-Bus in any case. For
C-Bus connections, this position must
be used when at least one XL IRC or
XL MC is connected to the C-Bus.

XD508 compatible; bus termination
disabled
XD508 compatible switch position for
C-Busses equipped only with XL500
family controllers with bus termination
disabled. This switch position must be
used if the BNA device is installed in
the middle of such a C-Bus.