SECTION 4. TROUBLESHOOTING
4-1. TROUBLESHOOTING GUIDE
PROBLEM
CAUSE
CORRECTION
The evaporator is iced-up
• The door was closed
• Open the door when following
after a De-icing Cycle
the de-icing procedure
• Evaporator temperature at end
• Increase the setting of Step 8 in
of De-icing Cycle too low
Programming Section
• Maximum time of De-icing Cycle
• Increase the setting of Step 7 in
too short
Programming Section
Too much water on
• The unit has been shut down
• Start a De-icing Cycle
evaporator fins
without a De-icing Cycle
Slow to decrease
• Temperature of room too high
• Ventilate the room
in temperature (decline in
performance)
• Back of unit too close to
• Change the location of the
the wall
unit
Slow to decrease
• Condenser obstructed by dirt
• Clean the condenser
in temperature (decline in
performance)
• Evaporator iced up
• Perform a De-icing Cycle
Display temperature does
• In Probe Mode, the display
• Normal
not match the actual inlet air
shows the product temperature
temperature (No alarm)
All indicator lights off and
• Check electrical supply
• Plug unit into receptacle, or
ON/OFF switch will not
reset wall circuit breaker
operate
• Fuse of control board blown
• Change the fuse