1.8.7.4.2.1 Connecting PRN-6F Printer

Remote printers require a primary AC power source. If required for the fire alarm
system configuration (for example, a Proprietary Fire Alarm System), a remote
printer requires a secondary power source (battery backup). Since a secondary
power source is not provided as a standard feature, a separate UL-listed
Uninterruptible Power Supply (UPS) should be used. The building emergency
power supply may be used, as long as it meets the power continuity requirements of
NFPA 72. Refer to NFPA 72 for further details.

Connect the remote printer to the FACP via the ANN-S/PG module using a standard
DB-25 cable. One end of the cable will plug into the DB-25 connector on the PRN
printer and the other end plugs into the parallel connector on the ANN-S/PG
module. Note that the 9-pin DB-9 port on the ANN-S/PG is used to connect a serial
printer. The 25-pin port is used for a Centronics parallel printer cable. Connect
either a serial or parallel printer, but not both at the same time.

1.8.7.4.2.2 Setting Printer Options

Refer to the documentation supplied with the PRN-6F printer for instructions on
using the printer menu controls. Set the printer options (under the menu area) as
shown in the following table:

Table 1.2 PRN Setup Options

Option

Setting

Option

Setting

Font

HS Draft

CPI

10CPI

LPI

6 LPI

Skip

0.5

ESC Character

ESC

Emulate

Epson FX-850

Bidirectional Copy

ON

I/O

CG-TAB

Graphic

Buffer

40K

Country

E-US ASCII

Serial

Auto CR

OFF

Baud

9600 or 2400

Color Option

Not Installed

Format

7 Bit, Even, 1 Stop

Formien

Protocol

XON/XOFF

Lines

6LPI=60

Character Set

Standard

Standard

Exec 10.5

SI.Zero

On

Auto LF

On

PAPER
BIN 1

12/72”

BIN 2

12/72”

SINGLE

12/72”

PUSH TRA

12/72”

PULL TRA

12/72”

PAP ROLL

12/72”

This manual is related to the following products: