NFPA Standard-Specific Requirements
202
MS-9200UDLS PN 52750:E1 01/27/09
C.1 Central Station/Remote Station Transmitter:
Connection to FACP Dry Contacts
The dry contacts of the FACP programmable relays can be used to trip a UL-864 Listed Central
Station/Remote Station Transmitter. The FACP contacts must be supervised by the Central Station/
Remote Station Transmitter module using End-of-Line Resistors (ELRs) with a value determined
by the Transmitter manufacturer. Power is also provided by the Central Station/Remote Station
Transmitter manufacturer. Refer to the Central Station/Remote Station Transmitter manufacturer’s
manual for details.
Figure C.4 FACP Dry Contacts Connection to Central Station/Remote Station Transmitter
Typical Central Station/Remote Station Transmitter Module
Typical Input Zone Triggers
FACP Main Circuit Board
Al
ar
m
T
roub
le*
Su
pe
rv
is
or
y
*Note: The Trouble Relay is a fail-safe
relay. With power applied to the FACP
and no troubles in the panel, the wiring
should be connected to the NO and C
contacts as indicated in the illustration.
ms9200udlsdryxmi