NFPA Standard-Specific Requirements

202

MS-9200UDLS PN 52750:E1 01/27/09

C.1 Central Station/Remote Station Transmitter:
Connection to FACP Dry Contacts

The dry contacts of the FACP programmable relays can be used to trip a UL-864 Listed Central
Station/Remote Station Transmitter. The FACP contacts must be supervised by the Central Station/
Remote Station Transmitter module using End-of-Line Resistors (ELRs) with a value determined
by the Transmitter manufacturer. Power is also provided by the Central Station/Remote Station
Transmitter manufacturer. Refer to the Central Station/Remote Station Transmitter manufacturer’s
manual for details.

Figure C.4 FACP Dry Contacts Connection to Central Station/Remote Station Transmitter

Typical Central Station/Remote Station Transmitter Module

Typical Input Zone Triggers

FACP Main Circuit Board

Al

ar

m

T

roub

le*

Su

pe

rv

is

or

y

*Note: The Trouble Relay is a fail-safe
relay. With power applied to the FACP
and no troubles in the panel, the wiring
should be connected to the NO and C
contacts as indicated in the illustration.

ms9200udlsdryxmi

t.cdr