beautypg.com

Honeywell MS-9200UDLSE User Manual

Page 127

background image

Programming

MS-9200UDLS PN 52750:E1 01/27/09

127

ANN-LED Point Option - Alarm, Trouble and Supervisory

If Point is selected as the module option, and the module is programmed to
annunciate alarms, troubles and supervisories, the first ten LEDs on the first
ANN-LED module will display the system status information. The remaining 30
LEDs on the first module and the last 30 LEDs on the remaining modules will
display the alarm, trouble and supervisory status for each of the ten zones in the
Point Range programmed for that particular module. The LED assignments for
each ANN-LED module will be as follows.

ANN-LED Module #1 (Point Range 01 - 10)

ANN-LED Module #2 (Point Range 11 - 20)

The LED assignments for the modules annunciating Point Ranges 21 - 30, 31 - 40
and 41 - 50, 51 - 60, 61 - 70, 71 - 80, 81 - 90 and 91 - 99, will follow the same
pattern as the second ANN-LED Module.

Alarm Silenced

NAC 1 Fault

NAC 2 Fault

NAC 3 Fault

NAC 4 Fault

Earth Fault

Battery Fault

Charger Fault

Disabled

Maintenance

Point 01

Active/Alarm

Point 02

Active/Alarm

Point 03

Active/Alarm

Point 04

Active/Alarm

Point 05

Active/Alarm

Point 01

Trouble

Point 02

Trouble

Point 03

Trouble

Point 04

Trouble

Point 05

Trouble

Point 01

Supervisory

Point 02

Supervisory

Point 03

Supervisory

Point 04

Supervisory

Point 05

Supervisory

Point 06

Active/Alarm

Point 07

Active/Alarm

Point 08

Active/Alarm

Point 09

Active/Alarm

Point 10

Active/Alarm

Point 06

Trouble

Point 07

Trouble

Point 08

Trouble

Point 09

Trouble

Point 10

Trouble

Point 06

Supervisory

Point 07

Supervisory

Point 08

Supervisory

Point 09

Supervisory

Point 10

Supervisory

Not Used

Not Used

Not Used

Not Used

Not Used

Not Used

Not Used

Not Used

Not Used

Not Used

Point 11

Active/Alarm

Point 12

Active/Alarm

Point 13

Active/Alarm

Point 14

Active/Alarm

Point 15

Active/Alarm

Point 11

Trouble

Point 12

Trouble

Point 13

Trouble

Point 14

Trouble

Point 15

Trouble

Point 11

Supervisory

Point 12

Supervisory

Point 13

Supervisory

Point 14

Supervisory

Point 15

Supervisory

Point 16

Active/Alarm

Point 17

Active/Alarm

Point 18

Active/Alarm

Point 19

Active/Alarm

Point 20

Active/Alarm

Point 16

Trouble

Point 17

Trouble

Point 18

Trouble

Point 19

Trouble

Point 20

Trouble

Point 16

Supervisory

Point 17

Supervisory

Point 18

Supervisory

Point 19

Supervisory

Point 20

Supervisory