MS-9200UDLS PN 52750:E1 01/27/09

31

1.8.7.4 ANN-S/PG Serial/Parallel Interface Installation

The ANN-S/PG Serial/Parallel Interface module allows the connection of a remote
serial or parallel printer to the FACP for a real-time log of system events, detector
status reports and event history. The module is provided with a plastic enclosure for
surface mounting. Proceed with the installation as described in the following:

1. Ensure that all power (AC and DC) has been removed from the FACP.

2. Connect the ANN-S/PG to the FACP as illustrated in Figure 1.6

3. Using the DIP switches on the back of the ANN-S/PG module, assign an ID

number (address) to the module

4. Select the address and configuration options for the ANN-S/PG module as

described in the Programming section of this manual (refer to "ANN-BUS
Options" on page 118)
Note that the Auto-configure feature allows the programmer to quickly bring all
installed ANN-BUS modules online (refer to "Auto-Configure" on page 128)

5. Connect a printer to the ANN-S/PG Parallel or Serial connectors (refer to Figure

1.6). Only one printer can be connected.

1.8.7.4.1 Specifications

Operating Voltage: 24 VDC

Current (Alarm and Standby): 45 mA

Ambient Temperature: 32

o

F to 120

o

F (0

o

C to 49

o

C)

Max. Wiring Distance from FACP: 6,000 ft. (1,800 m)

Mounting: Surface

Dimensions: 6”W x 7-3/4”H x 1-7/16”D (15.2 cm W x 19.7 cm H x 3.7 cm D)

For indoor use in a dry location only

1.8.7.4.2 PRN-6F Printer Installation

When connected to the FACP via the ANN-S/PG module, the PRN-6F prints the
status changes within the control panel and time-stamps the printout with the time
of day and date that the event occurred. It provides 80 columns of data on standard
9” x 11” tractor-feed paper. This section contains information on connecting a
printer to the control panel and setting the printer options.

Figure 1.6 ANN-S/PG Connection to FACP

ANN-S/PG Module

MS-9200UDLS

Cable Connectors for

connection to printer

Parallel

Serial

ANN-BUS and power wiring are
supervised and power-limited

24 VDC
nonresettable

ANN-BUS/ACS BUS

92udlst

ospg.c