6.4.2 Peer Status Codes
The following status codes can appear in register 4371.
Status Code
Description
0
Updating: All Normal
32
Normal Link Operation
64
Never Getting Token
96
Sole Station
128
Duplicate Station
6.4.3 Global Out Update Status
The following status codes can appear in register 4385.
Status Code
Description
0x01
Updating All OK
0x02
Not Assigned
0x04
Not Assigned
0x08
Global Update Timeout (not transmitted in 500 milliseconds)
0x10
Global Data Not Configured (length set to zero)
0x20
Not Assigned
0x40
Invalid Global Data Length (Length > 32 words)
0x80
Not Assigned.