Port Physical and Protocol Specifications

MBP ♦ ProLinx Gateway

Protocol Manual

Modbus Plus

Page 18 of 52

ProSoft Technology, Inc.

May 12, 2011

2.1

Functional Specifications - Modbus Plus

The Modbus Plus (MBP) protocol driver operates as a single, peer-to-peer
Modbus Plus port with dual media-redundant connectors. The two connectors
cannot be configured as separate MBP ports. They are for physical cabling
redundancy only.

General Parameters

Modbus Function
Codes

3: Read Multiple Data Registers (MSTR 2)
16: Write Multiple Data Register (MSTR 1)
Global data read (32 words per node max.)
Global data write (32 words per node max.)

Address Scope

1 to 64

Modbus Plus Functioning as a Master

Command List

Up to 200 commands on the master port, fully configurable for function,
slave address, register to/from addressing and word count

Polling of command list Configurable polling of command list, including continuous read or write

commands and write on change of data (Function Code 16 Write
command only)"

Modbus Plus Functioning as a Slave

Node address

1 to 64 (software selectable)