3.3
[Modbus Plus Commands]
The [Modbus Plus Commands] sections defines the commands to issue from the
module to other devices on the Modbus Plus network. Commands are entered in
the columns between the START and END labels. This section may contain up to
200 commands.
Example
Parameter Description
The following section lists the parameters.
3.3.1 Enable
This field defines how to execute the command:
Disable (0): disables the command. The command will not execute during the
normal polling sequence.
Continuous (1): executes the command during each scan of the command list
if the Poll Interval Time is set to zero (0). If the Poll Interval Time is set, the
command will be executed when the interval timer expires.
Event Command (2): The command executes only if the internal data
associated with the command changes. This value is only valid for WRITE
commands.
3.3.2 Internal Address
0 to 3999
This field specifies the internal database register to be associated with the
command.
If the command is a read function, the data read from the slave device will be
placed starting at the register value entered in this field.
If the command is a write function, the data written to the slave device will be
sourced from the address specified.