beautypg.com

Irritrol MC-E User Manual

Page 37

background image

Catastrophic Flow Sensor Protection (Optional Setup)

The MC-E provides a function to detect an unscheduled flow. Any detected flow in the system when no station is watering

is considered an unscheduled flow. The MC-E has the capability to monitor any unscheduled flow and activate Station 2

as a flow alarm to shut off a normally open master valve.

The flow alarm can be used to activate a normally open master valve which is installed ahead of the other valves on the

system. Station 2 must be set to flow alarm in SETUP for this to function. The F00 (“F00” represents the upper flow limit

for the main line) parameters in the flow setup will dictate the overflow threshold of the main line. When at any time MC-

E detects an unscheduled flow that violates F00 overflow parameters, MC-E will activate station 2 to close the normally

open master valve.

Install Critical Flow Shut off Master Valve

Step 1 – Find a location along the sub-main pipe that services

the irrigation system to install the normally open

master valve. The location should be ahead of any

valves in the irrigation system. Refer to the valves

installation instructions for further details.

Step 2 – Route a two-wire irrigation cable from the valve

to the controller. Connect one solenoid wire to the

valve common terminal and the remaining solenoid

wire to the Station 2 terminal.

Step 3 – Check for proper operation.

Configure Station for Flow Alarm Function

Step 1 – Place the Function dial to the SETUP

position.

Step 2 – Press

. Station 2 setup screen will be displayed.

Step 3 – Press the

button to configure Station 2 as flow alarm to activate a normally-open master valve or press the

button to configure it back to station. Press

to activate your selection.

Step 4 – Return the Function dial to AUTO/RUN

position.

Catastrophic Flow Parameters

Step 1 – To assign F00’s flow value (Catastrophic flow), place the Function dial to the FLOW SENSING

position. Navigate to the Over percentage limit screen by pressing the

button. If F00 is not the displayed

station number, press the

button repeatedly until F00 is selected.

Step 2 – Enter the desired catastrophic flow value and press

.

Do not set the Catastrophic flow value below the rated minimum flow of your flow sensor or it may

not function properly.

For example: If your flow sensor is rated at 20–300 GPM, DO NOT set the F00 flow value below 20 GPM.

Step 3 – Adjust the catastrophic Overflow. See “Set Overflow percentages” section.

Offset Value

Flow Unit

K Value

Size Code

Flow Sensor

Station 1

Station 3

Station 4

Flow

Normally Open

Master Valve

(Station 2)

COM

FLOW +

COM

Sta 2

FLOW – or

SENSOR

Sta 1

Sta 3

Sta 4