INSTALLATION (cont.)

Fire Alarm Control Panel Connection

(Input Signal Terminal E+ and E-)

The controller is equipped with a normal open input signal connection, which can

be connected directly from the fire alarm control panel. This input signal terminal

should only be connected to a close or open dry contact signal. When receiving

the signal from the fire alarm control panel, the unit turns off and does not turn back

on until it has been RESET.

Connecting Fire Alarm Control Panel to Controller

1. Remove three (3) screws from the upper panel on the control panel side and

open the upper panel.

2. Remove two (2) screws and plate from the right side panel.

SCREW (3)