INSTALLATION (cont.)

Wall Thermostat Connection

(Millivolt System ONLY: Option) (cont.)

Connecting Wall Thermostat to Unit

4. Set the wall thermostat to cooling system mode, since most wall thermostats

are designed for both heating and cooling.

5. Prepare the wire harness for connection from the unit to the thermostat.

Recommended wire type and size: Thermostat cable / Solid wire 16 ~ 26 AWG

6. Identify the thermostat connectors labeled G, Y, and RC.

G (Fan On/Off), Y (Cooling On/Off) and RC (Cooling Transfer - Common)

7. Connect the wire harness from the terminal of the unit to the thermostat

according to the labels shown below.

Note: Use thermostat that is compatible with millivolt system. Do not connect

thermostat to AC power source.

Wall Thermostat

Connector Name

Unit Connector Name

Function

RC

Y

G

RC

Y

G

Common

Cool On/Off

Fan On/Off

Unit

Thermostat

(Millivolt System)

G

Y

RC

GY

W

R

C

R

H

OB

Remove Factory-Installed Jumper