Appendix c: clock relay wiring diagram, Wired clock circuit installation – American Time Wireless Controller User Manual
Page 12
© American Time
12
SiteSync IQ Wireless Controller
Installation Manual
Appendix C: Clock Relay
Wiring Diagram
Appendix
Tr
oubleshooting
Operation
Contr
oller
Installation
Intr
oduction
Clock Code 01 - 3 wire Synchronous
NO
C
NC
C
NO
NC
BELL 5/CLK A
BELL 6/CLK B
CORRECTION
RETURN
RUN MOTOR
AC RTN
120/24 VAC
To install wired clock circuits:
1. Disconnect and lock out power to the SiteSync IQ Wireless Controller and any circuit wiring.
2. Remove the cover from the Wireless Controller.
a. Remove 2 screws from each side of the wire compartment cover.
b. Remove the wire compartment cover.
3. Route clock circuit wires into the wiring compartment of the Wireless Controller.
a. Remove knockout(s) below wire compartment.
b. Use copper conductors only.
c. Use strain relief connector fittings in the knockout holes to secure the wires.
d. Route the wires into the wiring compartment, leaving enough slack to make all connections to the relay terminals.
4. Connect clock wires to the circuit relay terminals.
5. Replace the wire compartment cover.
6. Apply power to the wireless controller and clock circuit(s).
7. Test the clock circuit. Clock relay B should activate at HH:57:54 for 8 seconds and at 05:57:54 for 14 seconds.
Wired Clock Circuit Installation